IEC 60502-1 600/1000V 2-5 Core Copper XLPE SWA LSZH Cable
600/1000V copper XLPE SWA LSZH cable to IEC 60502-1. Explore 2-4 core power cables, three-core plus earth variants and 5-core options, with dimensions and installation guidance.
600_1000V XLPE Insulated, LSZH Sheathed, Armoured PowerCables to IEC 60502-1 (2-4 Cores).pdf Contact us

APPLICATION

BURY CABLE XLPE SWA LSZH cable combines copper conductors, XLPE insulation, halogen free inner covering, steel wire armour and halogen free outer sheath for fixed 600/1000V power circuits.

The construction suits projects requiring mechanical protection alongside specified smoke and halogen performance. Applications include building distribution, industrial plants and infrastructure routes, with installation and burial conditions confirmed for the project.

STANDARDS

Basic design to IEC 60502-1.

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.

Insulation : Thermosetting XLPE material and thickness shall be as per IEC 60502-1.

Inner Covering : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Armouring : Steel wire armour.

Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour2-coreBrown and blue.
3-coreBrown, black and grey.
4-coreBlue, brown black and grey.
5-coreGreen and yellow, blue, brown black, grey.
Other colours can be offered upon request.
Sheath ColourBlack; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

circular copper conductors : 6 × Overall Diameter

shaped copper conductors : 8 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-RZ1MZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Inner Covering ThicknessNominal Armour Wire DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmmmmmkg/km
2 cores
2×1.520.71.00.81.813.2325
2×2.520.71.00.81.814.0372
2×420.71.00.81.815.1438
2×620.71.01.251.817.1645
2×1020.71.01.251.819.0806
2×1620.71.01.251.821.11015
2×2520.91.01.61.825.21517
2×3520.91.01.61.827.51830
2×5021.01.01.61.930.82259
2×7021.11.02.02.035.83182
2×9521.11.22.02.140.24022
2×12021.21.22.02.344.24810
2×15021.41.22.52.449.36120
2×18521.61.42.52.654.77375
2×24021.71.42.52.760.59037
2×30021.81.62.52.966.610871
2×40022.01.62.53.173.713256
3 cores
3×1.520.71.00.81.813.6368
3×2.520.71.00.81.814.5427
3×420.71.00.81.815.7514
3×620.71.01.251.817.8752
3×1020.71.01.251.819.8965
3×1620.71.01.251.822.11244
3×2520.91.01.61.826.51872
3×3520.91.01.61.829.02298
3×5021.01.01.61.932.52876
3×7021.11.02.02.138.04081
3×9521.11.22.02.242.75227
3×12021.21.22.02.346.86283
3×15021.41.42.52.552.88045
3×18521.61.42.52.758.19678
3×24021.71.42.52.864.311998
3×30021.81.62.53.070.814540
3×400221.63.153.380.018919
3 cores + 1 core earth conductor


3 cores1 core




3×16/1020.70.71.01.61.823.51363
3×25/1620.90.71.01.61.827.32054
3×35/1620.90.71.01.61.930.12480
3×50/2521.00.91.01.62.134.03167
3×70/3521.10.91.222.239.94476
3×95/5021.11.01.222.344.35757
3×120/7021.21.11.222.548.87047
3×150/7021.41.11.42.52.755.08812
3×185/9521.61.11.42.52.860.410723
3×240/12021.71.21.62.53.167.813326
3×300/15021.81.41.62.53.273.816169
3×400/18522.01.61.63.153.683.520955
4 cores
4×1.520.71.00.81.814.4414
4×2.520.71.00.81.815.4487
4×420.71.00.81.816.7617
4×620.71.01.251.819.0870
4×1020.71.01.251.821.31136
4×1620.71.01.61.824.51642
4×2520.91.01.61.828.62254
4×3520.91.01.61.931.62814
4×5021.01.02.02.136.53837
4×7021.11.22.02.241.95096
4×9521.11.22.02.346.76499
4×12021.21.42.52.552.98446
4×15021.41.42.52.758.010039
4×18521.61.42.52.863.712099
4×24021.71.62.53.171.515261
4×30021.81.62.53.278.018400
4×40022.01.83.153.688.724037
5 cores
5x1.520.71.00.81.814.8481
5×2.520.71.00.81.815.8571
5×420.71.00.81.817.2702
5×620.71.01.251.819.41020
5×1020.71.01.251.821.61345
5×1620.71.01.61.824.71944
5×2520.91.01.61.929.02810
5×3520.91.01.62.032.23398

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Air ambient temperature : 30°C

Ground ambient temperature : 20°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E4A

Conductor cross-ectional areaRef. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)Ref. Method D (direct in in groud or in ducting in groud. in or around buildings)
1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.
1234567
mm²AAAAAA
1.5272329252521
2.5363139333328
4494252444336
6625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
240607520636546395324
300698599732628446365
400787673847728--

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E4B

Conductor cross-sectional areaTwo-core cable, d.c.Two-core cable, single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.5313127
2.5191916
4121210
67.97.96.8
104.74.74.0
162.92.92.5


rxzrxz
251.851.850.1601.901.600.1401.65
351.351.350.1551.351.150.1351.15
500.980.990.1551.000.860.1350.87
700.670.670.1500.690.590.1300.60
950.490.500.1500.520.430.1300.45
1200.390.400.1450.420.340.1300.37
1500.310.320.1450.350.380.1250.30
1850.250.260.1450.290.220.1250.26
2400.1950.2000.1400.240.1750.1250.21
3000.1550.1600.1400.210.1400.1200.185
4000.1200.1300.1400.1900.1150.1200.165

Note :

r = conductor resistance at operating temperature

x = reactance

z = impedance

KEY FEATURES

  • 71 construction entries with Class 2 copper conductors.

  • Two-, three- and four-core sizes from 1.5 to 400 mm², plus three-core and earth variants.

  • Five-core entries from 1.5 to 35 mm².

  • Steel wire armour and ST8 halogen free sheath layers.

  • Bending radius: 6 × OD for circular conductors, 8 × OD for shaped conductors.

SELECTION NOTES

  • Confirm glands, armour bonding, earth-conductor arrangement and core colours with the installation design.

  • Electrical references cite BS 7671:2008 at 90°C conductor, 30°C air and 20°C ground. Apply the appropriate route and grouping corrections.

  • For 150 mm² three- and four-core cables, contact BURY CABLE for confirmed voltage-drop data before final cable selection.

  • For five-core orders, request the matching datasheet and electrical ratings from BURY CABLE. Specify sheath colour and optional environmental properties.

RELATED CABLE TYPES

FAQ

What armour does this product use?

The multicore construction uses steel wire armour. Use the separate AWA range for single-core armoured circuits.

Are five-core cables included?

Five-core construction rows cover 1.5–35 mm². Request the matching five-core datasheet and installation ratings with your enquiry.

Can it be installed underground?

Use the cable within an approved underground design, with suitable route protection, ground conditions, terminations and rating corrections.

Does the LSZH specification establish fire survival?

For circuits required to remain operational during fire, ask BURY CABLE for the specified circuit-integrity construction and evidence.

What details are needed for a quotation?

Send cores, conductor areas, length per run, load and fault duty, route conditions, sheath options and project standards.