IEC 60502-1 600/1000V Multicore Copper XLPE LSZH Unarmoured Cable
600/1000V multicore copper XLPE LSZH unarmoured cable to IEC 60502-1. View 2-5 core and control-cable configurations, dimensions, electrical reference data and selection notes.
600_1000V XLPE Insulated,LSZH Sheathed Power Cables to IEC 60502-1 (2-5 Cores & Multicore).pdf Contact us

APPLICATION

BURY CABLE multicore copper XLPE LSZH cable supports fixed low-voltage power and control circuits in buildings, industrial plants and infrastructure. Its unarmoured construction combines XLPE-insulated copper cores with an ST8 halogen free sheath.

The range includes two-, three- and four-core power cables, three-core plus earth configurations, and smaller multicore circuits. Select protected routes and the required core identification to suit the installation.

STANDARDS

Basic design to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.

Insulation : Thermosetting XLPE material and thickness shall be as per IEC 60502-1.

Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour2-coreBrown and blue.
3-coreBrown, black and grey.
4-coreBlue, brown black and grey.
5-coreGreen and yellow, blue, brown black, grey.
Above 5 CoresBlack cores with white numerals.
Other colours can be offered upon request.
Sheath ColourBlack; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

circular copper conductors OD≤25mm : 4 × Overall Diameter

circular copper conductors OD﹥25mm : 6 × Overall Diameter

shaped copper conductors : 8 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-RZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmkg/km
2 Cores
2×1.520.71.89.2117
2×2.520.71.810.0146
2×420.71.811.0190
2×620.71.812.0244
2×1020.71.813.6349
2×1620.71.815.4495
2×2520.91.818.4735
2×3520.91.820.6963
2×5021.01.823.61261
2×7021.11.826.81751
2×9521.11.930.22359
2×12021.22.033.72950
2×15021.42.237.53633
2×18521.62.341.64523
2×24021.72.546.75877
2×30021.82.651.47285
2×400222.958.99294
3 cores
3×1.520.71.89.6143
3×2.520.71.810.5183
3×420.71.811.6244
3×620.71.812.6321
3×1020.71.814.4472
3×1620.71.816.3681
3×2520.91.819.51027
3×3520.91.821.91360
3×5021.01.825.11795
3×7021.11.928.72530
3×9521.12.032.43441
3×12021.22.136.14307
3×15021.42.340.35276
3×18521.62.444.66607
3×24021.72.650.28593
3×30021.82.755.210668
3×40022.03.063.313570
3 cores + 1 core earth conductor


3 cores1 core


3×16/1020.70.71.818.3792
3×25/1620.90.71.822.11201
3×35/1620.90.71.824.71533
3×50/2521.00.91.828.22069
3×70/3521.10.92.033.12906
3×95/5021.11.02.137.63949
3×120/7021.21.12.342.05036
3×150/7021.41.12.446.66005
3×185/9521.61.12.652.27608
3×240/12021.71.22.859.09856
3×300/15021.81.43.065.212224
3×400/18522.01.63.273.215523
4 cores
4×1.520.71.810.4172
4×2.520.71.811.3223
4×420.71.812.5303
4×620.71.813.7402
4×1020.71.815.7599
4×1620.71.817.5873
4×2520.91.821.21328
4×3520.91.823.81767
4×5021.01.827.52339
4×7021.12.031.73326
4×9521.12.135.84505
4×12021.22.339.95669
4×15021.42.444.66948
4×18521.62.649.58701
4×24021.72.855.711322
4×30021.83.061.414105
4×40022.03.270.417943
Multicore
5×1.520.71.811.7212
5×2.520.71.812.8276
7×1.520.71.812.6264
7×2.520.71.813.8351
10×1.520.71.815.6360
10×2.520.71.817.2483
12×1.520.71.816.0408
12×2.520.71.817.8552
14×1.520.71.817.0459
14×2.520.71.818.7626
19×1.520.71.818.6585
19×2.520.71.820.7806
21×1.520.71.819.4638
21×2.520.71.821.7881
24×1.520.71.821.5724
24×2.520.71.824.11002
30×1.520.71.822.8866
30×2.520.71.825.51209
40×1.520.71.825.41108
40×2.520.71.928.71560
48×1.520.71.828.01307
48×2.520.71.931.61864
61×1.520.71.930.71631
61×2.520.72.034.72312

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E2A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)
1 two-core cable*, single-phase a.c. or d.c.1 three- or four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three- or four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three- or four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three- or four-core cable*, three-phase a.c.
123456789
mm²AAAAAAAA
1.518.516.52219.524222623
2.52522302633303632
43330403545404942
64238514458526354
105751696080718675
167668918010796115100
259989119105138119149127
35121109146128171147185158
50145130175154209179225192
70183164221194269229289246
95220197265233328278352298
120253227305268382322410346
150290259334300441371473399
185329295384340506424542456
240386346459398599500641538
300442396532455693576741621
400--625536803667865741

Note: With or without a protective conductor.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E2B

Conductor cross-sectional areaTwo-core cable, d.c.Two-core cable, single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.5313127
2.5191916
4121210
67.97.96.8
104.74.74.0
162.92.92.5


rxzrxz
251.851.850.1601.901.600.1401.65
351.351.350.1551.351.150.1351.15
500.980.990.1551.000.860.1350.87
700.670.670.1500.690.590.1300.60
950.490.500.1500.520.430.1300.45
1200.390.400.1450.420.340.1300.37
1500.310.320.1450.350.280.1250.30
1850.250.260.1450.290.220.1250.26
2400.1950.2000.1400.240.1750.1250.21
3000.1550.1600.1400.210.1400.1200.185
4000.1200.1300.1400.1900.1150.1200.165

Note :

r = conductor resistance at operating temperature

x = reactance

z = impedance

KEY FEATURES

  • 87 construction entries covering power and multicore control configurations.

  • Two-, three- and four-core power sizes from 1.5 to 400 mm².

  • Three-core plus earth variants; 5–61 core entries in the listed 1.5 and 2.5 mm² sizes.

  • Class 2 copper as listed; alternative conductor classes are optional.

  • 90°C maximum operation; 250°C short circuit for 5 seconds.

SELECTION NOTES

  • Select the exact core count and earth-conductor size. Confirm colours or numbered cores and the circuit function.

  • Match bending space to the circular or shaped conductor rule and selected cable diameter shown below.

  • Electrical tables cite BS 7671:2008 for two-core and three-/four-core circuits. Request application-specific ratings for five-core and larger multicore configurations.

  • Confirm grouping, ambient conditions and route protection. Specify optional UV, oil, hydrocarbon, rodent or termite protection when needed.

RELATED CABLE TYPES

FAQ

Are all core counts available in every size?

Use the individual construction rows. The small multicore entries use 1.5 or 2.5 mm²; the power-cable sections have their own ranges.

How are the cores identified?

The colour table specifies colours for up to five cores and black cores with white numerals above five cores; confirm the required scheme.

Can the table ratings be applied to 61 cores?

Request ratings based on loaded cores, grouping and duty. The displayed electrical tables refer to the stated two-, three- and four-core circuits.

When should I select an armoured version?

Choose additional mechanical protection where the route design requires it; compare the related SWA LSZH product.

What should I send to BURY CABLE?

Provide core arrangement, area, lengths, load, installation method and smoke, halogen and sheath requirements.