IEC 60502-1 600/1000V Triple Copper XLPE LSZH Unarmoured Cable
600/1000V triple copper XLPE LSZH unarmoured cable to IEC 60502-1. Compare 14 conductor sizes from 10-500 mm2, assembly dimensions, resistance and installation-specific current data.
600_1000V XLPE Insulated, LSZH Sheathed Power Cables to IEC 60502-1 (Triple Core).pdf Contact us

APPLICATION

BURY CABLE triple copper XLPE LSZH cable is intended for fixed 600/1000V distribution where a three-conductor arrangement and halogen free sheath are specified. The range uses copper conductors, XLPE insulation, HFFR outer sheath and polyester tape.

The product illustration shows three individually sheathed conductors. Use the assembly dimensions and the flat or trefoil electrical data to plan protected trays, ducts and other approved routes. Confirm the required arrangement with BURY CABLE when ordering.

STANDARDS

IEC 60228

IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : Flexible copper, class 2.

Insulation : Cross linked polyethylene XLPE.

Outer Sheath : Halogen free thermoplastic compound HFFR.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

Tape : Polyester tape.

COLOUR CODE

Insulation Colour : Natural.

Sheath Colour : Black, red and white or black, red and blue.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Overload maximum core temperature : 130°C

CONSTRUCTION PARAMETERS

ConductorFLP600-RZ1-R / N2XOH
No. of Cores × Cross- sectional AreaConductor ClassConductor DiamMin. Insulation ThickMin. Outer Sheath ThickApprox. Overall DiameterApprox. Weight
No.×mm²
mmmmmmmmkg/km
1024.10.70.97.7×22.7393
1625.30.70.98.8×26.0565
2526.60.90.910.5×31.2845
3527.80.90.911.7×34.81127
5029.31.00.913.5×40.21571
70211.31.11.015.8×47.12171
95212.81.11.017.4×51.92769
120214.51.21.119.5×58.23550
150216.21.41.221.8×65.14286
185218.01.61.224.0×71.75214
240220.71.71.226.9×80.46813
300223.21.81.329.9×89.38419
400226.52.01.534.0×101.611109
500230.32.21.638.5×115.114387

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Conductor Cross- sectional areaMax. DC Resist. Cond. 20°CPerm. Current Buried/Duct 20°CPerm. Current Rating In Air 30°C - flat formationCurrent Rating In Air 30°C - trefoilNominal Capacitance
mm²Ohm/kmAAApF/m
101.91587774445
161.2175105101593
250.7896141135549
350.554115176169637
500.386135216207682
700.272167279268750
950.206197342328840
1200.161223400383873
1500.129251464444843
1850.108281533510803
2400.0801324634607866
3000.0641365736703916
4000.0486426868823944
5000.0384481998946983

KEY FEATURES

  • 14 Class 2 copper sizes from 10 to 500 mm².

  • XLPE insulation, HFFR sheath and polyester tape.

  • Sheath colour combinations: black/red/white or black/red/blue.

  • 90°C maximum operation; 250°C short circuit for 5 seconds.

  • Tables include DC resistance, buried/duct and in-air current data, and nominal capacitance.

SELECTION NOTES

  • Confirm the three-conductor assembly layout, dimensions and termination space before ordering.

  • Use the electrical column for the route: buried/duct at 20°C, or air at 30°C in the stated flat or trefoil formation. Confirm installation correction factors.

  • The 130°C overload figure is a separate short-term condition; request the permitted duration and duty from BURY CABLE.

  • This is an unarmoured product. The additional single-core armoured illustration is a series reference; specify external route protection and the installation bending requirement.

RELATED CABLE TYPES

FAQ

Is this a common-sheath multicore cable?

The main illustration shows three individually sheathed conductors. Confirm the required assembly and dimensional drawing with BURY CABLE.

Is it intended for continuous flexing?

The table lists Class 2 copper for fixed installations. For repeated movement, request a cable designed for that duty.

Which current value should I use?

Use the column matching the burial or air condition and cable formation, then confirm the complete installation design.

Are sheath protection options available?

UV, oil, hydrocarbon, rodent and termite protection can be specified as options and confirmed in the supply specification.

What is needed for a quotation?

Send conductor size, circuit arrangement, run lengths, environment, sheath colours, installation method and project standards.