BURY CABLE supplies this 600/1000V multicore copper PVC insulated, PVC sheathed cable for fixed power distribution and suitable multicore circuits in industrial and commercial projects. Use protected trays, conduits or trunking where mechanical protection is provided by the installation.
Basic design adapted to IEC 60502-1
| Flame Retardance (Single Vertical Wire Test) | IEC 60332-1 |
600/1000V
| Conductor | Annealed copper wire, stranded according to BS EN 60228 class 2. |
| Insulation | PVC/A according to IEC 60502-1. |
| Inner Covering Option | Extruded PVC or polymeric compound. |
| Outer Sheath | Extruded PVC Type ST1/ST2 according to IEC 60502-1. |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
| Insulation Colour | Two-core: Brown, blue Three-core: Brown, black, grey. Alternatively, green-and-yellow, blue, brown Four-core: Blue, brown, black, grey. Alternatively, green-and-yellow, brown, black, grey Five-core: Green-and-yellow, blue, brown, black, grey Note: Depending on their intended use, the cables might be subject to the core colour requirements specified in BS 7671 or other standards, or in statutory requirements. |
| Sheath Colour | Black, other colours can be offered upon request |
| Maximum temperature range during operation (PVC) | 70°C |
| Maximum short circuit temperature (5 Seconds) | |
| Conductor cross-section ≤300 mm2 | 160°C |
| Conductor cross-section >300 mm2 | 140°C |
| Minimum bending radius | 12 x Overall Diameter |
| Conductor | FLP600-VV-R | |||||
|---|---|---|---|---|---|---|
| No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight | |
| No.xmm2 | mm | mm | mm | mm | ||
| 2 Cores | ||||||
| 2x1.5 | 2 | 0.8 | 1.8 | 9.6 | 120 | |
| 2x2.5 | 2 | 0.8 | 1.8 | 10.4 | 151 | |
| 2x4.0 | 2 | 1.0 | 1.8 | 12.2 | 212 | |
| 2x6.0 | 2 | 1.0 | 1.8 | 13.2 | 266 | |
| 2x10 | 2 | 1.0 | 1.8 | 14.8 | 370 | |
| 2x16 | 2 | 1.0 | 1.8 | 16.6 | 510 | |
| 2x25 | 2 | 1.2 | 1.8 | 19.6 | 740 | |
| 2x35 | 2 | 1.2 | 1.8 | 21.8 | 986 | |
| 2x50 | 2 | 1.4 | 1.8 | 25.2 | 1355 | |
| 2x70 | 2 | 1.4 | 1.9 | 28.1 | 1798 | |
| 2x95 | 2 | 1.6 | 2.0 | 32.4 | 2419 | |
| 2x120 | 2 | 1.6 | 2.1 | 35.4 | 3003 | |
| 2x150 | 2 | 1.8 | 2.2 | 39.2 | 3696 | |
| 2x185 | 2 | 2.0 | 2.4 | 43.3 | 4536 | |
| 2x240 | 2 | 2.2 | 2.5 | 48.9 | 5849 | |
| 2x300 | 2 | 2.4 | 2.7 | 54.0 | 7223 | |
| 2x400 | 2 | 2.6 | 2.9 | 61.5 | 9566 | |
| 3 Cores | ||||||
| 3x1.5 | 2 | 0.8 | 1.8 | 10.1 | 149 | |
| 3x2.5 | 2 | 0.8 | 1.8 | 10.9 | 192 | |
| 3x4.0 | 2 | 1.0 | 1.8 | 12.9 | 277 | |
| 3x6.0 | 2 | 1.0 | 1.8 | 13.9 | 354 | |
| 3x10 | 2 | 1.0 | 1.8 | 15.7 | 503 | |
| 3x16 | 2 | 1.0 | 1.8 | 17.6 | 707 | |
| 3x25 | 2 | 1.2 | 1.8 | 20.8 | 1040 | |
| 3x35 | 2 | 1.2 | 1.8 | 23.2 | 1401 | |
| 3x50 | 2 | 1.4 | 1.8 | 26.9 | 1942 | |
| 3x70 | 2 | 1.4 | 1.9 | 30.1 | 2589 | |
| 3x95 | 2 | 1.6 | 2.1 | 34.7 | 3514 | |
| 3x120 | 2 | 1.6 | 2.2 | 38 | 4372 | |
| 3x150 | 2 | 1.8 | 2.3 | 42.1 | 5390 | |
| 3x185 | 2 | 2.0 | 2.5 | 46.5 | 6615 | |
| 3x240 | 2 | 2.2 | 2.7 | 52.5 | 8576 | |
| 3x300 | 2 | 2.4 | 2.8 | 58 | 10564 | |
| 3x400 | 2 | 2.6 | 3.1 | 66.1 | 14049 | |
| 3 Cores+1 Earth Conductor | ||||||
| power conductor | earth conductor | |||||
| 3x 16/10 | 2 | 1.0 | 1.0 | 1.8 | 19.0 | 764 |
| 3x 25/16 | 2 | 1.2 | 1.0 | 1.8 | 22.6 | 1137 |
| 3x 35/16 | 2 | 1.2 | 1.0 | 1.8 | 25.3 | 1494 |
| 3x 50/25 | 2 | 1.4 | 1.2 | 1.9 | 29.6 | 2120 |
| 3x 70/35 | 2 | 1.4 | 1.2 | 2.0 | 33.2 | 2862 |
| 3x 95/50 | 2 | 1.6 | 1.4 | 2.2 | 38.4 | 3917 |
| 3x120/70 | 2 | 1.6 | 1.4 | 2.3 | 42.0 | 4973 |
| 3x150/70 | 2 | 1.4 | 1.2 | 2.5 | 46.6 | 5861 |
| 3x185/95 | 2 | 1.6 | 1.4 | 2.6 | 51.6 | 7321 |
| 3x240/120 | 2 | 1.6 | 1.4 | 2.9 | 58.3 | 9433 |
| 3x300/150 | 2 | 1.8 | 1.6 | 3.1 | 64.5 | 11714 |
| 3x400/185 | 2 | 2.0 | 1.6 | 3.3 | 73.5 | 15404 |
| 4 Cores | ||||||
| 4x1.5 | 2 | 0.8 | 1.8 | 10.8 | 180 | |
| 4x2.5 | 2 | 0.8 | 1.8 | 11.8 | 236 | |
| 4x4.0 | 2 | 1.0 | 1.8 | 14 | 346 | |
| 4x6.0 | 2 | 1.0 | 1.8 | 15.2 | 447 | |
| 4x10 | 2 | 1.0 | 1.8 | 17.1 | 642 | |
| 4x16 | 2 | 1.0 | 1.8 | 19.3 | 910 | |
| 4x25 | 2 | 1.2 | 1.8 | 22.9 | 1347 | |
| 4x35 | 2 | 1.2 | 1.8 | 25.6 | 1824 | |
| 4x50 | 2 | 1.4 | 1.9 | 29.9 | 2553 | |
| 4x70 | 2 | 1.4 | 2.0 | 33.5 | 3409 | |
| 4x95 | 2 | 1.6 | 2.2 | 38.7 | 4628 | |
| 4x120 | 2 | 1.6 | 2.3 | 42.3 | 5763 | |
| 4x150 | 2 | 1.8 | 2.5 | 46.9 | 7132 | |
| 4x185 | 2 | 2.0 | 2.6 | 51.9 | 8723 | |
| 4x240 | 2 | 2.2 | 2.9 | 58.6 | 11344 | |
| 4x300 | 2 | 2.4 | 3.1 | 64.8 | 14012 | |
| 4x400 | 2 | 2.6 | 3.3 | 73.8 | 18590 | |
| Multicore | ||||||
| 5x1.5 | 2 | 0.8 | 1.8 | 11.7 | 213 | |
| 7x1.5 | 2 | 0.8 | 1.8 | 12.6 | 270 | |
| 10x1.5 | 2 | 0.8 | 1.8 | 15.6 | 371 | |
| 12x1.5 | 2 | 0.8 | 1.8 | 16.1 | 424 | |
| 14x1.5 | 2 | 0.8 | 1.8 | 16.8 | 480 | |
| 19x1.5 | 2 | 0.8 | 1.8 | 18.6 | 619 | |
| 21x1.5 | 2 | 0.8 | 1.8 | 19.5 | 676 | |
| 24x1.5 | 2 | 0.8 | 1.8 | 21.6 | 769 | |
| 30x1.5 | 2 | 0.8 | 1.8 | 22.8 | 927 | |
| 40x1.5 | 2 | 0.8 | 1.8 | 27.7 | 1196 | |
| 48x1.5 | 2 | 0.8 | 1.9 | 28.2 | 1430 | |
| 61x1.5 | 2 | 0.8 | 1.9 | 30.9 | 1773 | |
| 5x2.5 | 2 | 0.8 | 1.8 | 12.8 | 281 | |
| 7x2.5 | 2 | 0.8 | 1.8 | 13.8 | 363 | |
| 10x2.5 | 2 | 0.8 | 1.8 | 17.2 | 503 | |
| 12x2.5 | 2 | 0.8 | 1.8 | 17.7 | 580 | |
| 14x2.5 | 2 | 0.8 | 1.8 | 18.6 | 660 | |
| 19x2.5 | 2 | 0.8 | 1.8 | 20.6 | 860 | |
| 21x2.5 | 2 | 0.8 | 1.8 | 21.6 | 941 | |
| 24x2.5 | 2 | 0.8 | 1.8 | 24 | 1072 | |
| 30x2.5 | 2 | 0.8 | 1.8 | 25.4 | 1302 | |
| 40x2.5 | 2 | 0.8 | 2.0 | 31.1 | 1720 | |
| 48x2.5 | 2 | 0.8 | 2.0 | 31.7 | 2039 | |
| 61x2.5 | 2 | 0.8 | 2.1 | 34.7 | 2557 | |
| Conductor Operating Temperature | 70°C |
| Ambient Temperature | 30°C |
| Conductor cross- sectional area | Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method G (in free air) Spaced by one cable diameter | ||||
|---|---|---|---|---|---|---|---|---|
| 1 two-core cables*, single-phase a.c. or d.c. | 1 three-core cable* or 1 four-core cable, three -phase a.c. | 1 two-core cables*, singlephase a.c. or d.c. | 1 three-core cable* or 1 four-core cable, three -phase a.c. | 1 two-core cables*, single-phase a.c. or d.c. | 1 three-core cable* or 1 four-core cable, three -phase a.c. | 1 two-core cables*, single-phase a.c. or d.c. | 1 three-core cable* or 1 four-core cable, three -phase a.c. | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| mm2 | A | A | A | A | A | A | A | A |
| 1.5 | 14 | 13 | 16.5 | 15 | 19.5 | 17.5 | 22 | 18.5 |
| 2.5 | 18.5 | 17.5 | 23 | 20 | 27 | 24 | 30 | 25 |
| 4.0 | 25 | 23 | 30 | 27 | 36 | 32 | 40 | 34 |
| 6.0 | 32 | 29 | 38 | 34 | 46 | 41 | 51 | 43 |
| 10 | 43 | 39 | 52 | 46 | 63 | 57 | 70 | 60 |
| 16 | 57 | 52 | 69 | 62 | 85 | 76 | 94 | 80 |
| 25 | 75 | 68 | 90 | 80 | 112 | 96 | 119 | 101 |
| 35 | 92 | 83 | 111 | 99 | 138 | 119 | 148 | 126 |
| 50 | 110 | 99 | 133 | 118 | 168 | 144 | 180 | 153 |
| 70 | 139 | 125 | 168 | 149 | 213 | 184 | 232 | 196 |
| 95 | 167 | 150 | 201 | 179 | 258 | 223 | 282 | 238 |
| 120 | 192 | 172 | 232 | 206 | 299 | 259 | 328 | 276 |
| 150 | 219 | 196 | 258 | 225 | 344 | 299 | 379 | 319 |
| 185 | 248 | 223 | 294 | 255 | 392 | 341 | 434 | 364 |
| 240 | 291 | 261 | 344 | 297 | 461 | 403 | 514 | 430 |
| 300 | 334 | 298 | 394 | 339 | 530 | 464 | 593 | 497 |
| 400 | - | - | 470 | 402 | 634 | 557 | 715 | 597 |
* with or without a protective conductor
| Nominal Cross Section Area | Two-core cable d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||||
| mm2 | mV/A/m | mV/A/m | mV/A/m | ||||
| 1.5 | 29 | 29 | 25 | ||||
| 2.5 | 18 | 18 | 15 | ||||
| 4.0 | 11 | 11 | 9.5 | ||||
| 6.0 | 7.3 | 7.3 | 6.4 | ||||
| 10 | 4.4 | 4.4 | 3.8 | ||||
| 16 | 2.8 | 2.8 | 2.4 | ||||
| r | x | z | r | x | z | ||
| 25 | 1.75 | 1.75 | 0.170 | 1.75 | 1.50 | 0.145 | 1.50 |
| 35 | 1.25 | 1.25 | 0.165 | 1.25 | 1.10 | 0.145 | 1.10 |
| 50 | 0.93 | 0.93 | 0.165 | 0.94 | 0.80 | 0.140 | 0.81 |
| 70 | 0.63 | 0.63 | 0.160 | 0.65 | 0.55 | 0.140 | 0.57 |
| 95 | 0.46 | 0.47 | 0.155 | 0.50 | 0.41 | 0.135 | 0.43 |
| 120 | 0.36 | 0.38 | 0.155 | 0.41 | 0.33 | 0.135 | 0.35 |
| 150 | 0.29 | 0.30 | 0.155 | 0.34 | 0.26 | 0.130 | 0.29 |
| 185 | 0.23 | 0.25 | 0.150 | 0.29 | 0.21 | 0.130 | 0.25 |
| 240 | 0.180 | 0.190 | 0.150 | 0.24 | 0.165 | 0.130 | 0.21 |
| 300 | 0.145 | 0.155 | 0.145 | 0.21 | 0.135 | 0.130 | 0.185 |
| 400 | 0.105 | 0.115 | 0.145 | 0.185 | 0.100 | 0.125 | 0.160 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance
Class 2 annealed copper, PVC/A insulation and PVC ST1/ST2 sheath, without metallic armour.
Tables cover 2-, 3- and 4-core power cables, 3 cores plus earth and listed multicore configurations up to 61 cores.
Maximum conductor operating temperature 70°C; the stated minimum bending radius is 12 times overall diameter.
Specify core count, power and protective conductor sizes, circuit duty, core identification, route and length. Match the selected construction to an actual table row; size ranges differ between core groups.
Check installation method, loaded cores, grouping, ambient conditions and voltage drop. The power-circuit rating tables do not establish a current rating for every 5-61 core configuration.
Confirm core colours against project requirements, and obtain the final dimensional and weight schedule from BURY CABLE before ordering. Additional sheath properties and flame tests must be specified.
No. Use a protected route or specify an armoured alternative where the installation requires it.
No. Use the relevant construction-table row; the multicore entries and power-cable entries have different ranges.
The schedule includes 3 cores plus an earth conductor. Confirm the required protective conductor size and identification.
Do not assume this. Ask BURY CABLE for a rating based on the actual number of loaded cores and installation conditions.
Provide core configuration, conductor sizes, length, core colours, installation conditions, required tests and delivery details.