BURY CABLE supplies this 600/1000V XLPE insulated wire armoured cable for fixed low voltage distribution in industrial plants, substations and infrastructure. Specify steel wire armour for the listed multicore design or aluminium wire armour for the stated single core design, with route suitability confirmed for the project.
Conductor : Solid or stranded copper
Insulation : XLPE
1 Core : Red or Black
2 Cores : Red, Black
3 Cores : Red, Yellow, Blue
4 Cores : Red, Yellow, Blue, Black
5 Cores : Red, Yellow, Blue, Black, Green
Above 5 cores : Black core printed with white numbers
Inner sheath : PVC. Color: black
Armor : Galvanized steel wires or aluminium wires for 1 core cable
Sheath : Special PVC. Color: black
Rated voltage : 600V/1000V
Fire retardance : IEC 60332-3-22
Operating temperature : -20~60°C
Max. conductor operating temperature : 90°C
Chemical resistance : Aliphatic and aromatic hydrocarbon resistance
| No. of Cores | Conductor Corss-section | Conductor Type | Diameter over Insulation | Diameter over Inner Sheath | Diameter over Armor | Min. O.D. | Max. O.D. | Approx. Weight |
|---|---|---|---|---|---|---|---|---|
| mm² | mm | mm | mm | mm | mm | kg/km | ||
| 1 | 25 | Stranded, Class 2 | 7.9 | 9.9 | 13.7 | 16.8 | 18.6 | 560 |
| 1 | 35 | Stranded, Class 2 | 8.9 | 10.9 | 14.7 | 17.75 | 19.6 | 669 |
| 1 | 50 | Stranded, Class 2 | 10.2 | 12.2 | 16.0 | 19.01 | 21.0 | 823 |
| 1 | 70 | Stranded, Class 2 | 12.0 | 14.0 | 17.8 | 20.76 | 22.9 | 1047 |
| 1 | 95 | Stranded, Class 2 | 13.55 | 15.6 | 19.4 | 22.31 | 24.6 | 1321 |
| 1 | 120 | Stranded, Class 2 | 15.26 | 17.3 | 21.1 | 23.96 | 26.4 | 1586 |
| 1 | 150 | Stranded, Class 2 | 16.97 | 19.0 | 22.8 | 25.61 | 28.2 | 1875 |
| 1 | 185 | Stranded, Class 2 | 19.05 | 21.0 | 24.9 | 27.64 | 30.5 | 2277 |
| 1 | 240 | Stranded, Class 2 | 21.6 | 23.6 | 27.4 | 30.26 | 33.4 | 2875 |
| 1 | 300 | Stranded, Class 2 | 24.2 | 26.2 | 30.0 | 32.98 | 36.4 | 3514 |
| 1 | 400 | Stranded, Class 2 | 27.7 | 30.1 | 33.9 | 36.96 | 40.8 | 4430 |
| 1 | 500 | Stranded, Class 2 | 31.4 | 33.8 | 37.6 | 40.74 | 44.9 | 5546 |
| 1 | 630 | Stranded, Class 2 | 36.2 | 38.6 | 42.4 | 45.59 | 50.3 | 7018 |
| 2 | 1.5 | Solid, Class 1 | 2.79 | 7.9 | 9.68 | 12.88 | 14.2 | 343 |
| 2 | 1.5 | Stranded, Class 2 | 2.9 | 8.2 | 10.0 | 13.19 | 14.6 | 358 |
| 2 | 2.5 | Solid, Class 1 | 3.15 | 8.6 | 10.4 | 13.58 | 15.0 | 388 |
| 2 | 2.5 | Stranded, Class 2 | 3.31 | 9.1 | 10.9 | 14.06 | 15.5 | 413 |
| 2 | 4 | Solid, Class 1 | 3.61 | 9.5 | 11.32 | 14.47 | 16.0 | 454 |
| 2 | 4 | Stranded, Class 2 | 3.83 | 10.2 | 12.0 | 15.13 | 16.7 | 491 |
| 2 | 6 | Stranded, Class 2 | 4.35 | 11.0 | 12.8 | 15.91 | 17.5 | 562 |
| 2 | 10 | Stranded, Class 2 | 5.25 | 12.8 | 15.3 | 18.33 | 20.2 | 831 |
| 2 | 16 | Stranded, Class 2 | 6.25 | 14.8 | 17.3 | 20.27 | 22.4 | 1044 |
| 2 | 25 | Stranded, Class 2 | 7.9 | 18.1 | 21.3 | 24.15 | 26.6 | 1576 |
| 2 | 35 | Stranded, Class 2 | 8.9 | 20.1 | 23.3 | 26.09 | 28.8 | 1899 |
| 2 | 50 | Stranded, Class 2 | 10.2 | 22.8 | 26.0 | 28.71 | 31.7 | 2331 |
| 2 | 70 | Stranded, Class 2 | 12.0 | 26.4 | 29.6 | 32.59 | 36.0 | 3025 |
| 2 | 95 | Stranded, Class 2 | 13.55 | 29.9 | 33.9 | 36.96 | 40.8 | 4086 |
| 2 | 120 | Stranded, Class 2 | 15.26 | 33.3 | 37.3 | 40.45 | 44.6 | 4886 |
| 2 | 150 | Stranded, Class 2 | 16.97 | 36.7 | 40.7 | 43.94 | 48.5 | 5772 |
| 2 | 185 | Stranded, Class 2 | 19.05 | 41.3 | 46.3 | 49.76 | 54.9 | 7515 |
| 2 | 240 | Stranded, Class 2 | 21.6 | 46.4 | 51.4 | 55.1 | 60.8 | 9278 |
| 2 | 300 | Stranded, Class 2 | 24.2 | 52.0 | 57.0 | 60.72 | 67.0 | 11248 |
| 3 | 1.5 | Solid, Class 1 | 2.79 | 8.3 | 10.13 | 13.32 | 14.7 | 368 |
| 3 | 1.5 | Stranded, Class 2 | 2.9 | 8.7 | 10.47 | 13.65 | 15.1 | 388 |
| 3 | 2.5 | Solid, Class 1 | 3.15 | 9.1 | 10.9 | 14.06 | 15.5 | 426 |
| 3 | 2.5 | Stranded, Class 2 | 3.31 | 9.6 | 11.44 | 14.59 | 16.1 | 451 |
| 3 | 4 | Solid, Class 1 | 3.61 | 10.1 | 11.9 | 15.04 | 16.6 | 506 |
| 3 | 4 | Stranded, Class 2 | 3.83 | 10.8 | 12.6 | 15.71 | 17.3 | 543 |
| 3 | 6 | Stranded, Class 2 | 4.35 | 11.7 | 13.5 | 16.59 | 18.3 | 631 |
| 3 | 10 | Stranded, Class 2 | 5.25 | 13.6 | 16.1 | 19.11 | 21.1 | 942 |
| 3 | 16 | Stranded, Class 2 | 6.25 | 15.8 | 18.3 | 21.24 | 23.4 | 1214 |
| 3 | 25 | Stranded, Class 2 | 7.9 | 19.4 | 22.6 | 25.41 | 28.0 | 1827 |
| 3 | 35 | Stranded, Class 2 | 8.9 | 21.5 | 24.7 | 27.45 | 30.3 | 2230 |
| 3 | 50 | Stranded, Class 2 | 10.2 | 24.4 | 27.6 | 30.46 | 33.6 | 2792 |
| 3 | 70 | Stranded, Class 2 | 12.0 | 28.7 | 32.7 | 35.6 | 39.3 | 3949 |
| 3 | 95 | Stranded, Class 2 | 13.55 | 32.1 | 36.1 | 39.28 | 43.3 | 4959 |
| 3 | 120 | Stranded, Class 2 | 15.26 | 35.8 | 39.8 | 43.07 | 47.5 | 5981 |
| 3 | 150 | Stranded, Class 2 | 16.97 | 39.9 | 44.9 | 48.4 | 53.4 | 7628 |
| 3 | 185 | Stranded, Class 2 | 19.05 | 44.4 | 49.4 | 52.96 | 58.4 | 9204 |
| 3 | 240 | Stranded, Class 2 | 21.6 | 50.3 | 55.3 | 59.07 | 65.2 | 11531 |
| 3 | 300 | Stranded, Class 2 | 24.2 | 55.9 | 60.9 | 64.89 | 71.6 | 13978 |
| 4 | 1.5 | Solid, Class 1 | 2.79 | 9.0 | 10.85 | 14.02 | 15.5 | 411 |
| 4 | 1.5 | Stranded, Class 2 | 2.9 | 9.4 | 11.24 | 14.4 | 15.9 | 427 |
| 4 | 2.5 | Solid, Class 1 | 3.15 | 9.9 | 11.72 | 14.86 | 16.4 | 479 |
| 4 | 2.5 | Stranded, Class 2 | 3.31 | 10.5 | 12.3 | 15.42 | 17.0 | 506 |
| 4 | 4 | Solid, Class 1 | 3.61 | 11.0 | 12.8 | 15.91 | 17.5 | 579 |
| 4 | 4 | Stranded, Class 2 | 3.83 | 11.9 | 13.7 | 16.78 | 18.5 | 621 |
| 4 | 6 | Stranded, Class 2 | 4.35 | 12.8 | 15.3 | 18.33 | 20.2 | 837 |
| 4 | 10 | Stranded, Class 2 | 5.25 | 15.0 | 17.5 | 20.47 | 22.6 | 1093 |
| 4 | 16 | Stranded, Class 2 | 6.25 | 17.4 | 20.6 | 23.47 | 25.9 | 1569 |
| 4 | 25 | Stranded, Class 2 | 7.9 | 21.4 | 24.6 | 27.35 | 30.2 | 2168 |
| 4 | 35 | Stranded, Class 2 | 8.9 | 23.9 | 27.1 | 29.97 | 33.1 | 2702 |
| 4 | 50 | Stranded, Class 2 | 10.2 | 27.1 | 30.3 | 33.27 | 36.7 | 3382 |
| 4 | 70 | Stranded, Class 2 | 12.0 | 31.8 | 35.8 | 38.99 | 43.0 | 4807 |
| 4 | 95 | Stranded, Class 2 | 13.55 | 35.6 | 39.6 | 42.87 | 47.3 | 6066 |
| 4 | 120 | Stranded, Class 2 | 15.26 | 40.1 | 45.1 | 48.6 | 53.6 | 7845 |
| 4 | 150 | Stranded, Class 2 | 16.97 | 44.3 | 49.3 | 52.86 | 58.3 | 9313 |
| 4 | 185 | Stranded, Class 2 | 19.05 | 49.3 | 54.3 | 58.1 | 64.1 | 11311 |
| 4 | 240 | Stranded, Class 2 | 21.6 | 55.9 | 60.9 | 64.89 | 71.6 | 14243 |
| 4 | 300 | Stranded, Class 2 | 24.2 | 62.2 | 67.2 | 71.39 | 78.8 | 17273 |
| 5 | 1.5 | Solid, Class 1 | 2.79 | 9.8 | 11.6 | 14.7 | 16.3 | 467 |
| 5 | 1.5 | Stranded, Class 2 | 2.9 | 10.3 | 12.1 | 15.23 | 16.8 | 480 |
| 5 | 2.5 | Solid, Class 1 | 3.15 | 10.8 | 12.6 | 15.7 | 17.3 | 546 |
| 5 | 2.5 | Stranded, Class 2 | 3.31 | 11.5 | 13.3 | 16.39 | 18.1 | 569 |
| 5 | 4 | Solid, Class 1 | 3.61 | 12.1 | 14.6 | 17.7 | 19.5 | 774 |
| 5 | 4 | Stranded, Class 2 | 3.83 | 13.0 | 15.5 | 18.53 | 20.4 | 816 |
| 5 | 6 | Stranded, Class 2 | 4.35 | 14.0 | 16.6 | 19.59 | 21.6 | 957 |
| 5 | 10 | Stranded, Class 2 | 5.25 | 16.5 | 19.0 | 21.92 | 24.2 | 1249 |
| 5 | 16 | Stranded, Class 2 | 6.25 | 19.2 | 22.4 | 25.22 | 27.8 | 1820 |
| 5 | 25 | Stranded, Class 2 | 7.9 | 23.7 | 26.9 | 29.58 | 32.6 | 2530 |
| 5 | 35 | Stranded, Class 2 | 8.9 | 26.4 | 29.6 | 32.4 | 35.7 | 3185 |
| 5 | 50 | Stranded, Class 2 | 10.2 | 30.3 | 34.3 | 37.34 | 41.2 | 4354 |
| 5 | 70 | Stranded, Class 2 | 12.0 | 35.2 | 39.2 | 42.49 | 46.9 | 5703 |
| 5 | 95 | Stranded, Class 2 | 13.55 | 39.8 | 44.8 | 48.11 | 53.1 | 7719 |
| 5 | 120 | Stranded, Class 2 | 15.26 | 44.4 | 49.4 | 52.96 | 58.4 | 9320 |
| 5 | 150 | Stranded, Class 2 | 16.97 | 49.0 | 54.0 | 57.81 | 63.8 | 11067 |
| 5 | 185 | Stranded, Class 2 | 19.05 | 55.0 | 60.0 | 64.02 | 70.6 | 13537 |
| 5 | 240 | Stranded, Class 2 | 21.6 | 61.9 | 66.9 | 71.1 | 78.4 | 16954 |
| 5 | 300 | Stranded, Class 2 | 24.2 | 69.3 | 75.6 | 79.93 | 88.2 | 21739 |
| 7 | 1.5 | Stranded, Class 2 | 2.9 | 10.8 | 12.7 | 15.81 | 17.4 | 518 |
| 7 | 2.5 | Stranded, Class 2 | 3.31 | 12.2 | 14.7 | 17.75 | 19.6 | 732 |
| 10 | 1.5 | Stranded, Class 2 | 2.9 | 13.9 | 16.4 | 19.4 | 21.4 | 796 |
| 10 | 2.5 | Stranded, Class 2 | 3.31 | 15.7 | 18.2 | 21.15 | 23.3 | 969 |
| 12 | 1.5 | Stranded, Class 2 | 2.9 | 14.4 | 16.9 | 19.88 | 21.9 | 864 |
| 12 | 2.5 | Stranded, Class 2 | 3.31 | 16.2 | 18.7 | 21.63 | 23.9 | 1047 |
| 14 | 1.5 | Stranded, Class 2 | 2.9 | 15.1 | 17.6 | 20.56 | 22.7 | 922 |
| 14 | 2.5 | Stranded, Class 2 | 3.31 | 17.1 | 19.6 | 22.5 | 24.8 | 1136 |
| 19 | 1.5 | Stranded, Class 2 | 2.9 | 16.8 | 19.3 | 22.21 | 24.5 | 1080 |
| 19 | 2.5 | Stranded, Class 2 | 3.31 | 19.1 | 22.3 | 25.12 | 27.7 | 1512 |
| 24 | 1.5 | Stranded, Class 2 | 2.9 | 19.8 | 23.0 | 25.8 | 28.5 | 1491 |
| 24 | 2.5 | Stranded, Class 2 | 3.31 | 22.5 | 25.7 | 28.42 | 31.4 | 1852 |
| 27 | 1.5 | Stranded, Class 2 | 2.9 | 20.2 | 23.4 | 26.19 | 28.9 | 1559 |
| 27 | 2.5 | Stranded, Class 2 | 3.31 | 23.0 | 26.2 | 28.91 | 31.9 | 1946 |
| 30 | 1.5 | Stranded, Class 2 | 2.9 | 21.0 | 24.2 | 26.97 | 29.7 | 1644 |
| 30 | 2.5 | Stranded, Class 2 | 3.31 | 23.9 | 27.1 | 29.97 | 33.1 | 2089 |
| 37 | 1.5 | Stranded, Class 2 | 2.9 | 22.8 | 26.0 | 28.71 | 31.7 | 1870 |
| 37 | 2.5 | Stranded, Class 2 | 3.31 | 25.9 | 29.1 | 31.91 | 35.2 | 2381 |
Solid or stranded copper, XLPE insulation, black PVC inner sheath and special PVC outer sheath.
Galvanized steel wire armour for multicore construction; aluminium wire armour for single core cable.
Maximum conductor operating temperature 90°C; published tables give conductor class, layer diameters, overall diameter limits and approximate weight.
State core count, conductor size and class, armour material, quantity and drum lengths. Confirm load rating, voltage drop, installation method, grouping and ambient conditions.
Match glands and accessories to the confirmed overall and armour diameters. Agree bonding and earthing arrangements; single core aluminium armour must be identified correctly in the order.
Confirm outdoor or burial conditions, chemical exposure and required flame-test documentation with BURY CABLE. The separate -20 to 60°C operating range is not the 90°C conductor limit.
No. The construction specifies aluminium wires for single core cable and galvanized steel wires for multicore cable.
Black PVC inner sheath and black special PVC outer sheath.
No. Use the armoured construction table for layer diameters, overall diameter and approximate weight.
It is the stated flame-retardance reference. It does not establish circuit integrity during fire.
Confirm the exact sheath, soil, moisture, mechanical conditions, installation rules and project requirements with BURY CABLE before selection.