APPLICATION
BS6724 four core LSZH armoured cable
is designed for fixed low voltage
power distribution.
It is suitable for buildings,
infrastructure projects, industrial facilities,
public utilities, plant rooms
and protected power distribution systems.
The cable uses stranded copper conductors
for reliable electrical performance
and practical installation.
The XLPE insulation provides good
electrical performance and thermal stability.
The LSZH sheath helps reduce smoke emission
and corrosive gas release in the event of fire.
The steel wire armoured construction
provides mechanical protection for
demanding installation routes.
This cable is commonly installed on cable trays,
in ducts, in risers, in plant rooms
and in protected underground routes.
Four core construction is commonly used
for three phase power systems
with neutral conductor.
It is suitable for applications where
low smoke zero halogen performance,
mechanical protection and fixed installation
are required.
The cable should be selected according to
voltage rating, number of cores,
conductor size, conductor material,
armour type, installation method
and project specification.
CONSTRUCTION
| Conductor | Solid Aluminum or Annealed Copper conductor, circular or shaped, Class 2 to BS EN60228. |
| Insulation | XLPE (Cross-Linked Polyethylene) Type GP 8 conforming to BS 7655-1.3 or type GP 6 conforming to BS 7655-1.2. |
| Colour Code | 1 Core : Brown or Blue |
| 2 Cores : Brown, Blue |
| 3 Cores : Brown, Black, Grey |
| 4 Cores : Blue, Brown, Black, Grey |
| 5 Cores : Green/Yellow, Blue, Brown, Black, Grey |
| Above 5 Cores : White Cores with black numbers |
| Bedding | The bedding shall consist of an extruded layer of polymeric material consistent with the operating temperature of the cable. |
| Armour | Single Core : AWA (Aluminum Wire Armour) |
| Multi Core : GSWA (Galvanized Steel Wire Armour) |
| Outer Sheath | LSOH (Low Smoke Zero Halogen),conforming to BS 7655-6.1. |
TECHNICAL INFORMATION
| Voltage rating | 600/1000V |
| Temperature rating | 0°C to +90°C |
| Bending radius | 1.5mm² to 16mm² : 6 x overall diameter |
| 25mm² and above : 8 x overall diameter |
| Flame retardant | BS EN 60332-1-2 ; BS EN 60332-3-24:2009 |
| Halogen free | BS EN 60754-1 |
| Smoke density | BS EN 61034-2 |
CABLE PARAMETER
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation Thickness | Nominal Bedding Thickness | Nominal Steel Wire Armor dia. | Nominal Sheath Thickness | Approx. Overall Diameter | Aprrox. Weight |
|---|
| mm² | No./mm | mm | mm | mm | mm | mm | kg/km |
|---|
| 4×1.5 | 7/0.53 | 0.7 | 0.8 | 0.9 | 1.4 | 13.3 | 390 |
| 4×2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 15.0 | 470 |
| 4×4 | 7/0.85 | 0.7 | 0.8 | 0.9 | 1.4 | 16.4 | 580 |
| 4×6 | 7/1.04 | 0.7 | 0.8 | 1.25 | 1.5 | 18.7 | 805 |
| 4×10 | 7/1.35 | 0.7 | 0.8 | 1.25 | 1.5 | 21.1 | 1090 |
| 4×16 | 7/1.70 | 0.7 | 0.8 | 1.25 | 1.6 | 23.4 | 1320 |
| 4×25 | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 28.9 | 1840 |
| 4x25* | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 26.1 | 1840 |
| 4×35 | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 31.9 | 2310 |
| 4x35* | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 28.6 | 2310 |
| 4×50* | 19/1.78 | 1.0 | 1 | 1.6 | 1.9 | 32.0 | 2970 |
| 4×70* | 19/2.14 | 1.1 | 1.2 | 2.0 | 2.1 | 37.7 | 4240 |
| 4×95* | 19/2.52 | 1.1 | 1.2 | 2.0 | 2.2 | 41.7 | 5400 |
| 4×120* | 37/2.03 | 1.2 | 1.4 | 2.5 | 2.3 | 47.1 | 7000 |
| 4×150* | 37/2.25 | 1.4 | 1.4 | 2.5 | 2.4 | 51.4 | 8350 |
| 4×185* | 37/2.52 | 1.6 | 1.4 | 2.5 | 2.6 | 56.6 | 10130 |
| 4×240* | 61/2.25 | 1.7 | 1.6 | 2.5 | 2.7 | 63.0 | 12840 |
| 4×300* | 61/2.52 | 1.8 | 1.6 | 2.5 | 2.9 | 68.8 | 15530 |
| 4×400* | 61/2.85 | 2 | 1.8 | 3.15 | 3.2 | 78.1 | 19950 |
* Shaped stranded conductor (class 2)
KEY FEATURES
- BS6724 standard construction
- 600/1000V voltage rating
- Four core power cable design
- XLPE insulated conductors
- LSZH bedding and outer sheath
- Steel wire armour for mechanical protection
- Low smoke and halogen-free performance
- Suitable for fixed low voltage distribution
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Cable size
- Cable length
- Number of cores
- Installation method
- Armour requirement
- Sheath colour
- Packing requirement
Four core BS6724 cable is commonly selected for three phase power distribution where a neutral conductor is required.
RELATED CABLE TYPES
- BS6724 single core armoured cable
- BS6724 three core armoured cable
- BS5467 armoured power cable
- IEC 60502 low voltage cable
- LSZH control cable
- Fire resistant power cable
FAQ
What is BS6724 four core cable used for?
BS6724 four core cable is used for fixed low voltage power distribution in buildings, infrastructure and industrial projects.
What does four core cable mean?
Four core cable normally includes three phase conductors and one neutral conductor for three phase power systems.
What is the difference between BS6724 and BS5467?
BS6724 uses LSZH materials. BS5467 is usually supplied with PVC bedding and sheath.
Can BURYCABLE supply BS6724 four core cable?
Yes. BURYCABLE can supply BS6724 four core cable according to project voltage, size, length and installation requirements.