This BS 6724 single-core aluminium cable is rated at 1900/3300V (1.9/3.3kV) and combines XLPE insulation, aluminium wire armour (AWA) and an LSZH outer sheath. It is intended for fixed power distribution in buildings, infrastructure, industrial facilities and substations where the specified circuit requires this voltage rating, mechanical protection and low-smoke, halogen-free sheathing.
The dedicated parameter table covers eight aluminium conductor sizes from 50 to 300 mm². Use the dimensions and weights on this page when planning the 1900/3300V installation, together with a project-specific assessment of circuit loading, voltage drop, fault duty and cable routing.
| Conductor | Solid Aluminum or Annealed Copper conductor, circular or shaped, Class 2 to BS EN60228. |
| Insulation | XLPE (Cross-Linked Polyethylene) Type GP 8 conforming to BS 7655-1.3 or type GP 6 conforming to BS 7655-1.2. |
| Colour Code | 1 Core : Brown or Blue |
| 2 Cores : Brown, Blue | |
| 3 Cores : Brown, Black, Grey | |
| 4 Cores : Blue, Brown, Black, Grey | |
| 5 Cores : Green/Yellow, Blue, Brown, Black, Grey | |
| Above 5 Cores : White Cores with black numbers | |
| Bedding | The bedding shall consist of an extruded layer of polymeric material consistent with the operating temperature of the cable. |
| Armour | Single Core : AWA (Aluminum Wire Armour) |
| Multi Core : GSWA (Galvanized Steel Wire Armour) | |
| Outer Sheath | LSOH (Low Smoke Zero Halogen),conforming to BS 7655-6.1. |
| Voltage rating | 1900/3300V |
| Temperature rating | 0°C to +90°C |
| Bending radius | 1.5mm² to 16mm² : 6 x overall diameter |
| 25mm² and above : 8 x overall diameter | |
| Flame retardant | BS EN 60332-1-2 ; BS EN 60332-3-24:2009 |
| Halogen free | BS EN 60754-1 |
| Smoke density | BS EN 61034-2 |
| Nominal Cross-sectional Area | Nominal Insulation Thickness | Nominal Bedding Thickness | Nominal Alum Wire Armor dia. | Nominal Sheath Thickness | Approx. Overall Diameter | Aprrox. Weight |
|---|---|---|---|---|---|---|
| mm² | mm | mm | mm | mm | mm | kg/km |
| 1x50 | 2 | 0.8 | 1.25 | 1.6 | 19.4 | 600 |
| 1x70 | 2 | 0.8 | 1.25 | 1.6 | 20.9 | 710 |
| 1x95 | 2 | 0.8 | 1.25 | 1.6 | 22.5 | 810 |
| 1x120 | 2 | 1 | 1.6 | 1.7 | 25.2 | 1065 |
| 1x150 | 2 | 1 | 1.6 | 1.7 | 26.5 | 1210 |
| 1x185 | 2 | 1 | 1.6 | 1.8 | 28.3 | 1390 |
| 1x240 | 2 | 1 | 1.6 | 1.8 | 30.5 | 1630 |
| 1x300 | 2 | 1 | 1.6 | 1.9 | 32.8 | 1900 |
1900/3300V single-core aluminium conductor construction.
Eight listed sizes: 50, 70, 95, 120, 150, 185, 240 and 300 mm².
XLPE insulation with a nominal thickness of 2 mm across the eight listed sizes.
Aluminium wire armour, polymeric bedding and an LSZH outer sheath.
Size-specific armour, sheath, overall diameter and weight data, with flame-retardance, halogen-content and smoke-density references in the original technical tables.
Specify the voltage and conductor details. State 1900/3300V, single-core aluminium and the required cross-sectional area. The general construction table combines several BS 6724 family options. Confirm the conductor form and class, final insulation grade and approved construction drawing for the selected size before ordering.
Use the dedicated AWA construction. Both the single-core construction entry and the parameter table identify aluminium wire armour. Confirm the circuit arrangement, armour bonding and earthing, core identification and termination requirements with the project designer. The general colour table lists brown or blue for one core; agree the required identification for the order.
Plan for the dimensions of this voltage-rated cable. The 1 x 50 mm² entry has an approximate overall diameter of 19.4 mm and weight of 600 kg/km; 1 x 300 mm² is listed at 32.8 mm and 1900 kg/km. All eight sizes fall within the technical table's 25 mm²-and-above bending-radius entry of 8 times the overall diameter. Confirm final production dimensions, handling requirements and the suitability of glands and terminations.
Define the route and delivery requirements. Provide the proposed tray, duct, riser or underground arrangement and any water, sunlight or chemical exposure. Confirm direct-burial suitability for the actual site conditions. Request a current-rating assessment for the installation; dimensions alone do not establish an allowable current. Include total length, drum lengths, sheath colour, test documents, packing and delivery destination.
Read the gallery as construction references. The retained images include three-core family illustrations as well as single-core views. A multicore drawing with steel wire armour does not define this single-core product. Use the dedicated parameter table and approved supply drawing for the ordered cable.
BS 6724 1900/3300V armoured LSZH cable range — review the family overview and project selection requirements.
BS 6724 1900/3300V single-core stranded copper conductor cable — compare the separate copper product and confirm its own construction and dimensions.
BS 6724 600/1000V single-core aluminium conductor cable — use the separate lower-voltage specification when required by the circuit.
This page covers 1900/3300V, equivalent to 1.9/3.3kV. The 600/1000V version has its own product page and parameter table; select the voltage rating required by the project.
The table lists 50, 70, 95, 120, 150, 185, 240 and 300 mm² single-core sizes. Each entry specifies 2 mm nominal insulation thickness. Other dimensions and approximate weights vary with conductor size.
The single-core construction entry and dedicated parameter table specify aluminium wire armour, abbreviated AWA. The steel wire armour shown in a multicore family illustration is not the specified armour for this single-core page.
Confirm the conductor form and class on the approved supply drawing or quotation for the selected size. The general construction wording combines family options and does not, by itself, resolve the conductor class for every order.
The original technical table lists 8 times the overall diameter for sizes of 25 mm² and above. All eight sizes here are within that range. Confirm the applicable installation and pulling requirements for the cable supplied.
Low-smoke and halogen-free properties do not establish circuit-integrity performance. The flame-retardance and smoke-related references listed here do not provide a fire survival duration; request product-specific test evidence if continued operation during fire is required.
Provide BS 6724, 1900/3300V, single-core aluminium conductor, cross-sectional area, AWA armour, total length and drum lengths. Include the required conductor form and class, insulation specification, core identification, installation conditions, sheath requirements, documents, packing and delivery details.