600/1000V Multicore Mica XLPE SWA LSZH Fire Resistant Cable to IEC 60502-1
600/1000V multicore copper fire resistant cable with mica glass tape, XLPE insulation and LSZH sheath. 2-5 core power configurations and three cores plus earth; swa construction.
600_1000V Mica+XLPE Insulated, LSZH SheathedPower Cables to IEC 60502-1 (2-5 Cores & Multicore).pdf Contact us

APPLICATION

BURY CABLE supplies this 600/1000V multicore mica XLPE LSZH cable for essential power circuits in buildings, transport facilities and industrial installations. The mica glass tape forms the fire barrier, while the LSZH sheath supports low-smoke and halogen-free requirements. Use ducts, trenches and routes requiring steel wire armour as part of the specified cable installation system.

STANDARDS

Basic design adapted from IEC 60502-1

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; EN 6387; BS 8491
Flame Retardance (single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.

Fire Barrier : Mica glass tape.

Insulation : Thermosetting XLPE material as per IEC 60502-1.

Inner Covering : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Armouring : Steel wire armour.

Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour

2-core : Brown and blue.

3-core : Brown, black and grey.

4-core : Blue, brown, black and grey.

5-core : Green-and-yellow, blue, brown, black, grey.

Other colours can be offered upon request.

Sheath Colour : Black; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius

circular copper conductors : 6 × Overall Diameter

shaped copper conductors : 8 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP600-mRZ1MZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Inner Covering ThicknessNominal Armour Wire DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmmmmmkg/km
2 cores
2×1.520.71.00.81.815.2393
2×2.520.71.00.81.816440
2×420.71.00.81.817.1507
2×620.71.01.251.819.1732
2×1020.71.01.251.821.0894
2×1620.71.01.251.823.11103
2×2520.91.01.61.827.21622
2×3520.91.01.61.829.51936
2×5021.01.01.61.932.82368
2×7021.11.02.02.037.83311
2×9521.11.22.02.142.24157
2×12021.21.22.02.346.24950
2×15021.41.22.52.451.36286
2×18521.61.42.52.656.77551
2×24021.71.42.52.762.59218
2×30021.81.62.52.968.611064
2×40022.01.62.53.175.713459
3 cores
3×1.520.71.00.81.815.8436
3×2.520.71.00.81.816.7495
3×420.71.00.81.817.9581
3×620.71.01.251.820.0838
3×1020.71.01.251.822.01050
3×1620.71.01.251.824.31328
3×2520.91.01.61.828.71973
3×3520.91.01.61.831.22398
3×5021.01.01.61.934.72976
3×7021.11.02.02.140.24200
3×9521.11.22.02.244.95346
3×12021.21.22.02.349.06402
3×15021.41.42.52.555.08187
3×18521.61.42.52.760.39822
3×24021.71.42.52.866.512141
3×30021.81.62.53.073.014682
3×40022.01.63.153.382.219088
3 cores + 1 core earth conductor


3 cores1 core




3×16/1020.70.71.01.61.825.61442
3×25/1620.90.71.01.61.829.52148
3×35/1620.90.71.01.61.932.32573
3×50/2521.00.91.01.62.136.13254
3×70/3521.10.91.222.242.04578
3×95/5021.11.01.222.346.65857
3×120/7021.21.11.222.551.07135
3×150/7021.41.11.42.52.757.28920
3×185/9521.61.11.42.52.862.510826
3×240/12021.71.21.62.53.169.913407
3×300/15021.81.41.62.53.276..016243
3×400/18522.01.61.63.153.685.721047
4 cores
4×1.520.71.00.81.816.8491
4×2.520.71.00.81.817.8565
4×420.71.00.81.819.1702
4×620.71.01.251.821.4968
4×1020.71.01.251.823.71233
4×1620.71.01.61.826.91755
4×2520.91.01.61.831.02369
4×3520.91.01.61.934.02928
4×5021.01.02.02.138.93972
4×7021.11.22.02.244.35233
4×9521.11.22.02.349.16636
4×12021.21.42.52.555.38608
4×15021.41.42.52.760.410203
4×18521.61.42.52.866.112264
4×24021.71.62.53.173.915427
4×30021.81.62.53.280.418565
4×40022.01.83.153.691.124233
5 cores
5x1.520.71.00.81.817.9578
5×2.520.71.00.81.819.0668
5×420.71.00.81.820.5799
5×620.71.01.251.822.91140
5×1020.71.01.251.825.41465
5×1620.71.01.61.829.02083
5×2520.91.01.61.933.82853
5×3520.91.01.62.037.13544

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Air ambient temperature : 30°C

Ground ambient temperature : 20°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E4A

Conductor cross-sectional areaRef. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)Ref. Method D (direct in in groud or in ducting in groud. in or around buildings)
1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.1 two-core cable, single-phase a.c. or d.c.1 three- or four-core cable, three-phase a.c.
1234567
mm²AAAAAA
1.5272329252521
2.5363139333328
4494252444336
6625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
240607520636546395324
300698599732628446365
400787673847728--

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E4B

Conductor cross-sectional areaTwo-core cables, d.c.Two-core cable, single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.5313127
2.5191916
4121210
67.97.96.8
104.74.74.0
162.92.92.5


rxzrxz
251.851.850.1601.901.600.1401.65
351.351.350.1551.351.150.1351.15
500.980.990.1551.000.860.1350.87
700.670.670.1500.690.590.1300.60
950.490.500.1500.520.430.1300.45
1200.390.400.1450.420.340.1300.37
1500.310.320.1450.350.380.1250.30
1850.250.260.1450.290.220.1250.26
2400.1950.2000.1400.240.1750.1250.21
3000.1550.1600.1400.210.1400.1200.185
4000.1200.1300.1400.1900.1150.1200.165

r = conductor resistance at operating temperature

x = reactance

z = impedance

KEY FEATURES

  • Class 2 plain or metal-coated annealed copper, with Class 1 and Class 5 offered as options; mica glass tape and thermosetting XLPE insulation.

  • ST8 inner covering, steel wire armour (SWA) and thermoplastic halogen-free ST8 outer sheath.

  • Construction schedule covers 2-5 core power configurations and three cores plus earth; conductor sizes vary by core arrangement.

SELECTION NOTES

  • Specify the required circuit-integrity test method, classification and duration together with compatible supports and terminations. Match the selected cable and installation system to the project fire strategy.

  • Apply the published current-rating and voltage-drop references to the matching circuit arrangement, installation method and temperatures, including the applicable correction factors.

  • The stated minimum is 6 times overall diameter for circular copper conductors and 8 times for shaped copper conductors. State any UV, oil, hydrocarbon, rodent or termite sheath options in the order.

RELATED CABLE TYPES

FAQ

What is the role of the mica glass tape?

It forms the fire barrier around the conductor and supports the cable design for circuit integrity during fire testing.

What does LSZH mean?

Low Smoke Zero Halogen. The sheath is a thermoplastic halogen-free ST8 compound, with smoke and gas test references listed in the fire-performance table.

Which construction sizes are listed?

The construction schedule covers 2-5 core power configurations and three cores plus earth. Select the exact row for conductor size, diameter and weight.

What mechanical protection does this version use?

ST8 inner covering, steel wire armour (SWA) and thermoplastic halogen-free ST8 outer sheath. Select accessories and bonding for this armour material.

What are the conductor temperature limits?

The stated maximum operating temperature is 90°C and the maximum short-circuit temperature is 250°C for 5 seconds.