BS 7846 Mica XLPE SWA LSZH Fire Resistant Cable - 600/1000V, 2-5 Core & Multicore
600/1000V armoured fire resistant cable with Class 2 copper conductors, mica glass tape, XLPE insulation and an LSZH sheath. BS 7846 design with 2-5 core and multicore sizes listed in the technical tables.
600_1000V Mica+XLPE Insulated, LSZH Sheathed,Armoured Power Cables to BS 7846 (2-5 Cores & Multicore).pdf Contact us

APPLICATION

BURY CABLE BS 7846 Mica XLPE SWA LSZH cable is intended for fixed 600/1000V power circuits where the project calls for an armoured, fire resistant construction with low smoke and halogen-free materials. The standard construction combines Class 2 copper conductors, mica glass tape, XLPE insulation, galvanized steel wire armour and an LSZH outer sheath.

Typical project settings include power stations, underground transport facilities, airports, hospitals, hotels, high-rise buildings and industrial installations. Select the cable for the specified circuit duty, route and environmental conditions. The construction tables cover 2-5 core power cable arrangements and additional multicore sizes.

For essential-services circuits, confirm the required fire test classification and the applicability of the supporting test report to the supplied cable. Cable selection must also account for current capacity, voltage drop, fault conditions, supports, terminations and the installation method.

KEY FEATURES

  • Annealed copper conductors with Class 2 stranding.

  • Mica glass tape fire barrier with XLPE type GP 8 insulation in the standard construction.

  • Galvanized steel wire armour and an LSZH outer sheath for the specified armoured cable design.

  • Construction data for 2, 3, 4 and 5 cores, plus 7, 12, 19, 27 and 37 cores. Use the table row for the required size.

  • Rated thermal limits: 90°C maximum operating temperature and 250°C short-circuit temperature for 5 seconds. These are not fire survival ratings.

STANDARDS

Basic design to BS 7846

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; EN 6387; BS 8491
Flame Retardance (single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : Annealed copper wire, stranded according to BS EN 60228 class 2.

Fire Barrier : Mica glass tape.

Insulation : XLPE type GP 8 according to BS 7655-1.3. HEPR type GP 6 according to BS 7655-1.2 or crosslinked polyolefin material type EI 5 according to BS EN 50363-5 can be offered as option.

Bedding : Extruded layer of polymeric material.

Armouring : Galvanized steel wire.

Outer Sheath : Extruded layer of polymeric material LTS 1 according to BS 7655-6.1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour

2-core : Brown and blue.

3-core : Brown, black and grey.

4-core : Blue, brown, black and grey.

5-core : Green-and-yellow, blue, brown, black, grey.

Sheath Colour : Black; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 8 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP600-mRZ1MZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Bedding ThicknessNominal Steel Wire Armour DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmmmmmkg/km
2 cores
2×1.5a20.60.80.91.313.5345
2×2.5a20.70.80.91.414.9413
2×4a20.70.80.91.416.0478
2×4a&c20.70.81.251.416.7581
2×6a20.70.80.91.417.2555
2×6a&c20.70.81.251.417.9666
2×10a20.70.80.91.519.2708
2×10a&c20.70.81.251.519.9832
2×16a20.70.81.251.522.01036
2×25a20.90.81.251.625.71386
2×25b20.90.81.251.623.51311
2×35a20.91.01.61.729.01918
2×35b20.91.01.61.726.51814
2×50b21.01.01.61.828.52330
2×70b21.11.01.61.932.02968
2×95b21.11.22.02.036.04085
2×120b21.21.22.02.139.04846
2×150b21.41.22.02.242.06223
2×185b21.61.42.52.448.07479
2×240b21.71.42.52.552.09137
2×300b21.81.62.52.657.010937
2×400b22.01.62.52.862.013316
3 cores
3×1.5a20.60.80.91.314.1384
3×2.5a20.70.80.91.415.6467
3×4a20.70.80.91.416.8551
3×4a&c20.70.81.251.417.5659
3×6a20.70.80.91.418.0652
3×6a&c20.70.81.251.418.7768
3×10a20.70.81.251.520.9985
3×16a20.70.81.251.623.41269
3×25a20.91.01.61.728.41953
3×25b20.91.01.61.726.51874
3×35a20.91.01.61.831.02393
3×35b20.91.01.61.828.52286
3×50b21.01.01.61.832.02952
3×70b21.11.01.61.935.03852
3×95b21.11.22.02.140.05312
3×120b21.21.22.02.244.06364
3×150b21.41.42.52.349.08113
3×185b21.61.42.52.453.09706
3×240b21.71.42.52.658.012045
3×300b21.81.62.52.763.014536
3×400b22.01.62.52.970.017866
4 cores
4×1.5a20.60.80.91.315.1433
4×2.5a20.70.80.91.416.7532
4×4a20.70.80.91.418.1637
4×4a&c20.70.81.251.418.8856
4×6a20.70.81.251.520.3901
4×10a20.70.81.251.522.61159
4×16a20.70.81.251.625.31516
4×25a20.91.01.61.730.82341
4×25b20.91.01.61.729.52286
4×35a20.91.01.61.833.72898
4×35b20.91.01.61.832.02824
4×50b21.01.01.61.935.03628
4×70b21.11.22.02.141.05188
4×95b21.11.22.02.245.06585
4×120b21.21.42.52.350.08520
4×150b21.41.42.52.455.010071
4×185b21.61.42.52.660.012149
4×240b21.71.62.52.766.015217
4×300b21.81.62.52.970.018373
4×400b22.01.83.153.281.023960
5 cores
5×1.520.60.80.91.416.3495
5×2.520.70.80.91.418.0603
5×420.70.80.91.519.7739
5×4b20.70.81.251.520.4869
5×620.70.81.251.521.91031
5×1020.70.81.251.624.61356
5×1620.71.01.61.728.72010
5×2520.91.01.61.833.62762
5×3520.91.01.61.936.93440
5×5021.01.22.02.042.44700
5×7021.11.22.02.248.26186
Multicore
7×1.520.60.80.91.417.5574
7×1.5c20.60.81.251.418.2687
7×2.520.70.80.91.419.3711
7×2.5c20.70.81.251.420.0837
7×420.70.81.251.521.81024
12×1.520.60.81.251.622.7968
12×2.520.70.81.251.625.51218
12×420.70.81.251.528.81725
19×1.520.61.01.61.626.11255
19×2.520.70.81.61.730.51844
19×420.71.01.61.733.22285
27×1.520.61.01.61.731.71856
27×2.520.61.01.61.735.72367
27×420.71.01.61.939.22993
37×1.520.71.01.61.734.92223
37×2.520.71.01.61.739.42878
37×420.71.22.02.044.84109

a Circular or compacted circular stranded conductor (Class 2).

b Shaped stranded conductor (Class 2).

c Cables with alternative armour wire size.


SELECTION NOTES

  • Specify voltage, number of cores, conductor cross-section, circuit duty and required length. Check the exact table row for dimensions and approximate weight.

  • Check load current, installation method, grouping, ambient temperature, voltage drop and short-circuit duty before choosing a conductor size.

  • The stated minimum bending radius is 8 times the overall cable diameter. Confirm routing space, gland selection, armour bonding and termination requirements for the installation.

  • Fire test references do not by themselves establish a classification or duration for every cable size. Confirm the required test conditions, classification and size coverage against the applicable report.

  • HEPR type GP 6 and crosslinked polyolefin type EI 5 are optional insulation alternatives. UV, hydrocarbon, oil, rodent and termite resistance are also options to agree before ordering.

  • For outdoor, buried, wet or chemically exposed routes, confirm the selected sheath option and installation protection. Use the project specification to determine suitability.

RELATED CABLE TYPES

BS 7629-1 Mica and Silicone Rubber Screened Cable, 300/500V
For comparison where a screened lower-voltage mica and silicone rubber construction is specified.

BS 7629-1 Silicone Rubber Screened Cable, 300/500V
A separate silicone rubber insulated, screened construction; check its own data and fire test evidence.

BS 7211 XLPE LSZH Building Cable with CPC, 300/500V
For building wiring applications with different voltage and construction requirements. It is not a like-for-like replacement for this armoured fire resistant cable.

FAQ

Is this the standard Mica XLPE version?

Yes. The standard construction uses a mica glass tape fire barrier and XLPE type GP 8 insulation. HEPR type GP 6 and crosslinked polyolefin type EI 5 are listed as options and must be specified separately.

Which core arrangements are listed?

The construction tables include 2, 3, 4 and 5 cores, together with 7, 12, 19, 27 and 37 cores. Available cross-sections, dimensions and approximate weights are given by individual table rows.

Does this page establish a CWZ, PH or timed fire rating?

No specific CWZ, PH or fire survival duration is assigned here. Confirm any project-required classification against a test report covering the supplied construction and size.

Does LSZH mean that any LSZH cable is fire resistant?

LSZH describes low smoke and halogen-free material characteristics. A circuit-integrity requirement needs its own applicable fire test evidence; it is not established by the LSZH description alone.

What information is needed for an enquiry?

Provide the voltage, core count, conductor size, quantity, installation method, operating environment and any required fire test classification. Include the project specification and any special sheath requirements.