BURY CABLE supplies N2XY copper power cable for fixed distribution at 0.6/1kV and 50 Hz in industrial installations and urban networks. XLPE insulation, PVC filler and a PVC outer jacket form an unarmoured construction for ducts, conduits, trays and sheltered outdoor routes. Underground installation is selected to suit the cable and site conditions.
VDE-0276 Part-603, HD 603.1, IEC 60502, VDE 0482-332-1-2, DIN EN 60332-1-2 / IEC 60332-1, CE Low Voltage Directive 73/23/EEC and 93/68/EEC, ROHS compliant
| Solid or stranded, plain copper conductor |
| to DIN VDE 0295 cl. 1 or cl. 2, BS 6360 cl. 1 or cl. 2 and IEC 60228 cl. 1 or cl. 2 |
| XLPE insulation type DIX3 acc. to VDE 0276-603/5G |
| Color coded to DIN VDE 0293(HD 308) |
| PVC filler |
| PVC outer jacket DMV6 to HD 603.1 |
| Working voltage | 600/1000 volts |
| Test voltage | 4000 volts |
| Minimum bending radius | 15 x Ø |
| Flexing Temperature | -5º C to +70º C |
| Fixed installation temperature | - 30º C to +70º C |
| Short circuit temperature | +250º C |
| Flame-retardant | IEC 60332.1 |
| Insulation resistance | >20 MΩ x km |
Class 1 solid or Class 2 stranded plain copper conductor.
XLPE insulation type DIX3, colour-coded cores, PVC filler and PVC outer jacket type DMV6.
The technical table specifies 600/1000V working voltage, 4000V test voltage and a minimum bending radius of 15 times overall diameter.
Specify core count, conductor size and class, route length, circuit load, installation method and required core identification. Size the cable using the conditions of the installed circuit.
Apply the product-specific temperature ranges in the technical table: -30 to +70°C for fixed installation and -5 to +70°C for flexing during handling. Plan mechanical protection for the selected route.
Use the PVC-sheathed N2XY construction for the specified service; the related N2XH range provides a separate LSZH sheath option for projects with halogen-free requirements.
IEC 60502-1 600/1000V Copper XLPE Lead Sheathed STA/ATA Cable
Fire resistant alternative: 600/1000V Multicore Mica XLPE LSZH Fire Resistant Cable to IEC 60502-1
Plain copper conductors, XLPE insulation, PVC filler and a PVC outer jacket.
The working voltage is 600/1000V, also expressed as 0.6/1kV.
Class 1 solid and Class 2 stranded copper are listed in the construction.
At least 15 times the overall cable diameter, as stated in the technical characteristics.
N2XY uses PVC. The related N2XH construction uses an LSZH or halogen-free sheath; select the cable and installation conditions for the project.