N2XY 0.6/1kV Copper XLPE PVC Power Cable to IEC 60502-1
N2XY 0.6/1kV copper power cable with XLPE insulation, PVC filler and PVC outer jacket. An unarmoured construction for fixed distribution circuits in industrial installations and urban networks.
N2XY.pdf Contact us

APPLICATION

BURY CABLE supplies N2XY copper power cable for fixed distribution at 0.6/1kV and 50 Hz in industrial installations and urban networks. XLPE insulation, PVC filler and a PVC outer jacket form an unarmoured construction for ducts, conduits, trays and sheltered outdoor routes. Underground installation is selected to suit the cable and site conditions.

Standard and Approval

  • VDE-0276 Part-603, HD 603.1, IEC 60502, VDE 0482-332-1-2, DIN EN 60332-1-2 / IEC 60332-1, CE Low Voltage Directive 73/23/EEC and 93/68/EEC, ROHS compliant

Cable Construction

Solid or stranded, plain copper conductor
to DIN VDE 0295 cl. 1 or cl. 2, BS 6360 cl. 1 or cl. 2 and IEC 60228 cl. 1 or cl. 2
XLPE insulation type DIX3 acc. to VDE 0276-603/5G
Color coded to DIN VDE 0293(HD 308)
PVC filler
PVC outer jacket DMV6 to HD 603.1

Technical Characteristics

Working voltage600/1000 volts
Test voltage4000 volts
Minimum bending radius15 x Ø
Flexing Temperature-5º C to +70º C
Fixed installation temperature- 30º C to +70º C
Short circuit temperature+250º C
Flame-retardantIEC 60332.1
Insulation resistance>20 MΩ x km

KEY FEATURES

  • Class 1 solid or Class 2 stranded plain copper conductor.

  • XLPE insulation type DIX3, colour-coded cores, PVC filler and PVC outer jacket type DMV6.

  • The technical table specifies 600/1000V working voltage, 4000V test voltage and a minimum bending radius of 15 times overall diameter.

SELECTION NOTES

  • Specify core count, conductor size and class, route length, circuit load, installation method and required core identification. Size the cable using the conditions of the installed circuit.

  • Apply the product-specific temperature ranges in the technical table: -30 to +70°C for fixed installation and -5 to +70°C for flexing during handling. Plan mechanical protection for the selected route.

  • Use the PVC-sheathed N2XY construction for the specified service; the related N2XH range provides a separate LSZH sheath option for projects with halogen-free requirements.

RELATED CABLE TYPES

FAQ

What does the N2XY construction contain?

Plain copper conductors, XLPE insulation, PVC filler and a PVC outer jacket.

What voltage is this cable rated for?

The working voltage is 600/1000V, also expressed as 0.6/1kV.

Which conductor types are available?

Class 1 solid and Class 2 stranded copper are listed in the construction.

What bending radius is specified?

At least 15 times the overall cable diameter, as stated in the technical characteristics.

How does the sheath differ from N2XH?

N2XY uses PVC. The related N2XH construction uses an LSZH or halogen-free sheath; select the cable and installation conditions for the project.