300/500V 2-3 Core Mica XLPE LSZH Fire Resistant Cable | BS7211 / BS6387
300/500V Mica XLPE LSZH fire resistant cable with 2 or 3 insulated cores and a bare copper CPC. Basic design adapted from BS7211, with BS6387 circuit integrity performance subject to test report confirmation.
300_500V Mica+XLPE Insulated, LSZH Sheathed Power Cablesto BS 7211 (2-3 Cores).pdf Contact us

APPLICATION

BURYCABLE FirePro 300/500V Mica XLPE LSZH cable

is designed for fixed installations where

circuit integrity under fire conditions

is specified.


This range comprises two or three insulated

copper cores and a separate bare copper

circuit protective conductor (CPC),

enclosed within an LSZH outer sheath.


Typical project environments include

hospitals, hotels, high-rise buildings,

airports, metro facilities and power stations.


Each insulated core incorporates a mica glass

tape fire barrier beneath the XLPE insulation.

The barrier helps preserve electrical insulation

during fire exposure.


The LSZH sheath helps limit smoke emission

and halogen acid gas release during burning.


The basic cable design is adapted from

BS 7211:2012. The catalogue lists BS 6387

and IEC 60331-21 as circuit integrity

test references.


The required test method, classification

and fire duration must be confirmed against

the relevant test report for the supplied cable.


This is an unarmoured fixed installation cable.

Provide additional mechanical protection

where required by the installation conditions.


For fire-resistant wiring systems, cable supports,

joints and terminations should be selected

to suit the specified circuit duty.


Select the cable according to voltage rating,

number of insulated cores, main conductor size,

CPC size, installation conditions and the

project fire performance requirements.


STANDARDS

Basic design adapted from BS 7211:2012

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; BS 6387
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen freeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

FIRE PERFORMANCE NOTE


The catalogue lists BS 6387 and IEC 60331-21

as circuit integrity test references.


IEC 60331-21 is a legacy reference.

The applicable standard edition, classification

and fire duration must be confirmed against

project requirements and the relevant

cable test report.


A specific CWZ classification or fire duration

must not be assumed from the product name

or the presence of mica tape alone.

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Annealed copper conductor, solid or stranded according to BS EN 60228 class 1 or class 2.

Fire Barrier : Mica glass tape.

Insulation : XLPE type GP 8 according to BS 7655-1.3. Crosslinked polyolefin material type EI 5 according to EN 50363-5 can be offered as option.

CPC (Circuit Protective Conductor) : Uninsulated copper conductor.

Outer Sheath : Extruded LSZH type LTS 2 according to BS 7655-6.1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour :

Twin : Brown and blue or, for 2x1.0 and 2x1.5 cables, brown and brown.

Three cores : Brown, black (centre core) and grey.

Position of CPC :

Twin : Centrally placed between cores in same plane.

Three cores : Centrally placed between black and grey cores in same plane.

Sheath Colour : White; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

OD<8mm : 4 × Overall Diameter

8mm≤OD≤12mm : 5 × Overall Diameter

OD>12mm : 6 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP300-mRZ1-U/R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessCrosssectional Area of CPCClass of CPCNominal Sheath ThicknessMin. Overall DimensionsMax. Overall DimensionsApprox. Weight
No.×mm² mmmm² mmmmmmkg/km
2×1.010.71.010.95.1×9.66.0×11.284
2×1.510.71.010.95.4×10.16.3×11.7101
2×2.510.71.511.05.9×11.37.0×12.2136
3×1.010.71.010.95.1×13.06.0×15.1108
3×1.510.71.010.95.4×13.76.3×15.9135
3×2.510.71.511.05.9×15.07.0×17.6190
2×1.020.71.010.95.2×9.86.1×11.489
2×1.520.71.010.95.5×10.36.4×12.0107
2×2.520.71.511.06.0×11.57.1×13.4141
2×420.71.511.06.5×12.47.7×14.6181
2×620.72.511.17.2×14.08.5×16.6256
2×1020.74.021.28.3×16.59.8×19.5406
2×1620.76.021.39.4×19.011.1×22.5576
3×420.71.511.06.5×17.07.7×19.9216
3×620.72.511.17.2×19.27.5×22.5311
3×1020.74.021.28.3×22.59.8×26.6460
3×1620.76.021.39.4×25.811.1×30.6690

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

CURRENT-CARRYING CAPACITIES (AMP) ACCORDING TO BS 7671:2008 TABLE 4E2A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)
1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three-phase a.c.
123456789
mm²AAAAAAAA
1.014.513171519172118
1.518.516.52219.524222623
2.52522302633303632
43330403545404942
64238514458526354
105751696080718675
167668918010796115100

Note: *With or without a protective conductor.

VOLTAGE DROP (PER AMP PER METER) ACCORDING TO BS 7671:2008 TABLE 4E2B

Conductor cross-sectional areaTwo-core cable, d.c.Two-core cable, single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.0464646
1.5313131

KEY FEATURES


- 300/500V rated voltage

- Two or three insulated cores plus a bare copper CPC

- Class 1 solid or Class 2 stranded copper main conductors

- Mica glass tape fire barrier

- XLPE insulation and LSZH outer sheath

- Unarmoured construction for fixed installation

- Basic design adapted from BS 7211

- Fire performance confirmed against the relevant test report



SELECTION NOTES


For quotation, specify the number of insulated

cores, main conductor cross-sectional area,

CPC cross-sectional area and total cable length.


Confirm whether Class 1 solid or Class 2

stranded main conductors are required.


Provide the required circuit integrity

test standard, classification and duration.


Also confirm insulation colours, sheath colour,

installation environment, packing requirements

and delivery destination.


The CPC is a protective conductor.

It must not be treated as an additional

insulated circuit core or neutral conductor.


Outdoor exposure, wet locations and underground

installation require assessment of the cable

construction and installation protection.


Additional UV, oil or chemical resistance

must be specified and confirmed before supply.



RELATED CABLE TYPES


300/500V Mica XLPE LSZH Single Core Cable with CPC


450/750V Mica XLPE LSZH Single Core Cable


450/750V Mica XLPE LSZH Multicore Cable


BS7211 LSZH Fixed Wiring Cable



FAQ


How many cores does this cable have?


This range has two or three insulated cores,

plus a separate bare copper circuit protective

conductor (CPC).


The CPC is not included in the stated number

of insulated cores.



What is the difference between the two versions?


The two-core version contains two insulated

cores plus CPC.


The three-core version contains three insulated

cores plus CPC.


Choose the configuration according to the

circuit design and required core identification.



Are the main conductors solid or stranded?


The catalogue includes Class 1 solid and

Class 2 stranded copper main conductors.


Confirm the conductor class and available

cross-sectional area before ordering.



What is the purpose of the mica tape?


Mica glass tape forms a fire barrier beneath

the XLPE insulation.


It helps preserve electrical insulation

during fire exposure. The resulting circuit

integrity performance must be supported

by testing of the cable construction.



Is LSZH performance the same as fire resistance?


No. LSZH concerns smoke and halogen-related

emissions during burning.


Fire resistance concerns maintaining circuit

integrity under defined fire test conditions.


These are separate performance requirements.



What standards are referenced for this cable?


The basic design is adapted from BS 7211:2012.


The catalogue lists BS 6387 and IEC 60331-21

as circuit integrity test references.

IEC 60331-21 is a legacy reference.


Confirm the applicable standard edition

and required performance before ordering.



Does this cable automatically have a CWZ rating?


No specific CWZ classification or fire duration

should be assumed from the catalogue title

or the presence of mica tape alone.


The required rating must be verified against

the relevant test report.



Is this cable armoured?


No. This is an unarmoured LSZH sheathed cable

with a separate bare copper CPC.


Additional mechanical protection should be

provided where required by the installation.



How do I request a quotation from BURYCABLE?


Send the required core configuration,

main conductor size, CPC size, conductor class,

cable length and fire performance requirements.


Include the installation environment,

colour requirements, packing details

and delivery destination.