IEC 60502-1 600/1000V Single Core Copper XLPE AWA PVC Cable
600/1000V single-core copper XLPE AWA PVC cable to IEC 60502-1. View 21 sizes from 1.5-1000 mm2, aluminium wire armour, dimensions, sheath options and electrical reference data.
600_1000V XLPE Insulated, PVC Sheathed, Armoured PowerCables to IEC 60502 (Single Core).pdf Contact us

APPLICATION

BURY CABLE single-core XLPE AWA PVC cable combines a stranded copper conductor with XLPE insulation, inner covering, aluminium wire armour and PVC outer sheath for fixed 600/1000V power distribution.

The armoured construction is intended for industrial, building and infrastructure routes requiring mechanical protection. Select cable formation, glands, supports and armour bonding as part of the complete circuit design.

STANDARDS

The product strictly adheres to the IEC 60502-1 international standard for fundamental design and manufacturing.

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)IEC 60332-1

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

ConductorAnnealed copper wire, stranded according to IEC 60228 class 2.
InsulationXLPE according to IEC 60502-1.
Inner CoveringExtruded PVC or polymeric compound.
ArmouringAluminium wire
Outer SheathExtruded PVC Type ST1/ST2 according to IEC 60502-1.
Outer Sheath OptionUV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation ColourBrown or blue, other colours can be offered upon request.
Sheath ColourBlack, other colours can be offered upon request.

MECHANICAL AND ELECTRICAL PROPERTIES

Maximum temperature range during operation80°C (For ST1 Sheath); 90°C (For ST2 Sheath)
Maximum short circuit temperature (5 Seconds) 250°C
Minimum bending radius
Circular copper conductors6 x Overall Diameter
Shaped copper conductors8 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-RVMAV-R
No. of Cores × Cross SectionClass of ConductorNominal Insulation ThicknessNominal Inner Covering ThicknessNominal Armour Wire DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.xmm² mmmmmmmmmmkg/km
1x1.520.71.00.81.810.2150
1x2.520.71.00.81.810.6169
1x4.020.71.00.81.811.2196
1x6.020.71.00.81.811.7228
1x1020.71.00.81.812.7290
1x1620.71.00.81.813.7372
1x2520.91.00.81.815.4507
1x3520.91.01.251.817.5681
1x5021.01.01.251.819.0848
1x7021.11.01.251.821.01116
1x9521.11.01.61.824.01511
1x12021.21.01.61.825.81821
1x15021.41.01.61.827.82165
1x18521.61.01.61.830.42655
1x24021.71.01.61.933.53352
1x30021.81.02.02.037.54224
1x40022.01.22.02.241.35263
1x50022.21.22.02.344.27379
1x63022.41.22.52.449.89611
1x80022.61.42.52.655.311896
1x100022.81.42.52.760.414467

ELECTRICAL PROPERTIES

Conductor Operating Temperature90°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) according to BS 7671: 2008 table 4E3A

Conductor cross-sectional areaReference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray, horizontal or vertical)
TouchingTouchingSpaced by on cable diameter
2 cables, single-phase a.c. or d.c. flat3 or 4 cables, threep-hase a.c. flat2 cables, single-phase a.c. or d.c. flat3 or 4 cables, three-phase a.c. flat3 cables threep-hase a.c. trefoil2 cables, d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
HorizontalVerticalHorizontalVerticalHorizontalVertical
123456789101112
mm2AAAAAAAAAAA
50237220253232222284270282266288266
70303277322293285356349357337358331
95367333389352346446426436412425393
120425383449405402519497504477485449
150488437516462463600575566539549510
185557496587524529688660643614618574
240656579689612625815782749714715666
300755662792700720943906842805810755
40085371789976781511371094929889848797
5009627911016851918131412661032989923871
6301082861114693510271528147411391092992940
80011709041246987111918091744120411551042978
10001261961134510551214210020261289123811101041

Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4E3B

Nominal Cross Section Area2 cables d.c.Ref. Methods C&F(clipped direct, on trays or in free air)
2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
TouchingSpaced*Trefoil and touchingFlat and touchingFlat and spaced*
1234567
mm2mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m


rxzrxzrxzrxzrxz
500.980.990.211.00.980.291.00.860.180.870.640.250.880.840.330.9
700.670.680.200.710.690.290.750.590.1700.620.600.250.650.620.320.70
950.490.510.1950.550.530.280.600.440.1700.470.460.240.520.490.310.58
1200.390.410.1900.450.430.270.510.350.1650.390.380.240.440.410.300.51
1500.310.330.1850.380.360.270.450.290.1600.330.310.230.390.340.290.45
1850.250.270.1850.330.300.260.400.230.1600.280.260.230.340.290.290.41
2400.1950.210.1800.280.240.260.350.1800.1550.240.210.220.300.240.280.37
3000.1550.170.1750.250.1950.250.320.1450.1500.210.1700.220.280.200.270.34
4000.1150.1450.1700.220.1800.240.300.1250.1500.1950.1600.210.270.200.270.33
5000.0930.1250.1700.210.1650.240.290.1050.1450.1800.1450.200.250.1900.240.31
6300.0730.1050.1650.1950.1500.230.270.0920.1450.1700.1350.1950.240.1750.230.29
8000.0560.0900.1600.1900.1450.230.270.0860.1400.1650.1300.1800.230.1750.1950.26
10000.0450.0920.1550.1800.1400.210.250.0800.1350.1550.1250.1700.210.1650.1800.24

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance

KEY FEATURES

  • 21 Class 2 copper sizes from 1.5 to 1000 mm².

  • Aluminium wire armour and PVC ST1/ST2 sheath options.

  • 80°C operating limit for ST1 sheath; 90°C for ST2 sheath.

  • 250°C short-circuit limit for 5 seconds.

  • Minimum bending radius: 6 × OD for circular conductors, 8 × OD for shaped conductors.

SELECTION NOTES

  • Choose single-core AWA terminations and bonding appropriate to the circuit arrangement and fault duty.

  • Electrical tables cite BS 7671:2008 at 90°C conductor and 30°C ambient. Obtain ratings appropriate to the supplied sheath grade and actual installation.

  • Construction sizes extend below the electrical table range; request electrical data for the specific size and route.

  • Include underground conditions, grouping, sheath colour and any optional UV, hydrocarbon, oil or pest protection in the enquiry.

RELATED CABLE TYPES

FAQ

Is this steel wire armoured cable?

This single-core product uses aluminium wire armour. The multicore PVC product uses galvanized steel wire armour.

Which sheath grade should I specify?

Choose the ST1 or ST2 requirement with BURY CABLE according to operating temperature and the project specification.

How do flat and trefoil layouts affect selection?

The electrical tables distinguish cable formations and spacing. Use the layout selected by the circuit designer.

Is the PVC sheath LSZH?

For low smoke zero halogen performance, compare the related AWA LSZH cable and confirm the required tests.

What is needed for a quotation?

Send size, lengths, load and fault duty, formation, route conditions, sheath grade, termination requirements and project standards.