600/1000V single core copper fire resistant cable with mica glass tape, XLPE insulation and LSZH sheath. 1.5-1000 mm2 Class 2 sizes; unarmoured construction.
600_1000V Mica+XLPE Insulated, LSZH Sheathed PowerCables to IEC 60502-1 (Single Core).pdf Contact us

APPLICATION

BURY CABLE supplies this 600/1000V single core mica XLPE LSZH cable for essential power circuits in buildings, transport facilities and industrial installations. The mica glass tape forms the fire barrier, while the LSZH sheath supports low-smoke and halogen-free requirements. Use protected trays, ducts, conduits and trunking as part of the specified cable installation system.

STANDARDS

Basic design adapted from IEC 60502-1

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; EN 6387; BS 8491
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.

Fire Barrier : Mica glass tape.

Insulation : Thermosetting XLPE compound as per IEC 60502-1.

Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour : Brown or blue; other colours can be offered upon request.

Sheath Colour : Black; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius

circular copper conductors OD≤25mm : 4 × Overall Diameter

circular copper conductors OD﹥25mm : 6 × Overall Diameter

shaped copper conductors : 8 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP600-mRZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmkg/km
1×1.520.71.46.858
1×2.520.71.47.271
1×420.71.47.892
1×620.71.48.3118
1×1020.71.49.3168
1×1620.71.410.3238
1×2520.91.412.0352
1×3520.91.413.2463
1×5021.01.414.7606
1×7021.11.416.7843
1×9521.11.518.81139
1×12021.21.520.61416
1×15021.41.622.81736
1×18521.61.625.02154
1×24021.71.728.12798
1×30021.81.830.93479
1×40022.01.934.54419
1×50022.22.038.25535
1×63022.42.243.07113
1×80022.62.347.99026
1×100022.82.453.011302

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method F (in free air or on a perforated cable tray, horizontal or vertical etc.) TouchingRef. Method G (in free air) Spaced by one cable diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phasea.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phasea.c. or d.c. or 3 cablesthree-phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.5191723202523-----
2.5262331283431-----
4353142374641-----
6454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--68358486879394086882310851008
500--783666990904108399894612531169
630--9007641130103312541151108814541362
800----1288117913581275121415811485
1000----1443132315201436134917751671

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E3B

Conductor cross-sectional area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)Ref. Methods A&B(enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²AAAAAAAA
2.51919191916161616
41212121210101010
67.97.97.97.96.86.86.86.8
104.74.74.74.74.04.04.04.0
162.92.92.92.92.52.52.52.5


rxzrxzrxzrxzrxzrxzrxz
251.851.850.311.901.850.1901.851.850.281.851.600.271.651.600.1651.601.600.1901.601.600.271.65
351.351.350.291.351.350.1801.351.350.271.351.150.251.151.150.1551.151.150.1801.151.150.261.20
500.991.000.291.050.990.1801.000.990.271.000.870.250.900.860.1550.870.860.1800.870.860.260.89
700.680.700.280.750.680.1750.710.680.260.730.600.240.650.590.1500.610.590.1750.620.590.250.65
950.490.510.270.580.490.1700.520.490.260.560.440.230.500.430.1450.450.430.1700.460.430.250.49
1200.390.410.260.480.390.1650.430.390.250.470.350.230.420.340.1400.370.340.1650.380.340.240.42
1500.320.330.260.430.320.1650.360.320.250.410.290.230.370.280.1400.310.280.1650.320.280.240.37
1850.250.270.260.370.260.1650.300.250.250.360.230.230.320.220.1400.260.220.1650.280.220.240.33
2400.1900.210.260.330.200.1600.250.1950.250.310.1850.220.290.1700.1400.220.1700.1650.240.1700.240.29
3000.1550.1750.250.310.1600.1600.220.1550.250.290.1500.220.270.1400.1400.1950.1350.1600.210.1350.240.27
4000.1200.1400.250.290.1300.1550.200.1250.240.270.1250.220.250.1100.1350.1750.1100.1600.1950.1100.240.26
5000.0930.1200.250.280.1050.1550.1850.0980.240.260.1000.220.240.0900.1350.1600.0880.1600.1800.0850.240.25
6300.0720.1000.250.270.0860.1550.1750.0780.240.250.0880.210.230.0740.1350.1500.0710.1600.1700.0680.230.24
8000.056-0.0720.1500.1700.0640.240.25-0.0620.1300.1450.0590.1550.1650.0550.230.24
10000.045-0.0630.1500.1650.0540.240.24-0.0550.1300.1450.0500.1550.1650.0470.230.24

Note : *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance

KEY FEATURES

  • Class 2 plain or metal-coated annealed copper, with Class 1 and Class 5 offered as options; mica glass tape and thermosetting XLPE insulation.

  • Unarmoured construction with a thermoplastic halogen-free ST8 outer sheath.

  • Construction schedule: 1.5-1000 mm² single-core Class 2 copper.

SELECTION NOTES

  • Specify the required circuit-integrity test method, classification and duration together with compatible supports and terminations. Match the selected cable and installation system to the project fire strategy.

  • Apply the published current-rating and voltage-drop references to the matching circuit arrangement, installation method and temperatures, including the applicable correction factors.

  • Circular conductors use 4 times overall diameter up to 25 mm cable diameter and 6 times above 25 mm; shaped conductors use 8 times overall diameter. State any UV, oil, hydrocarbon, rodent or termite sheath options in the order.

RELATED CABLE TYPES

FAQ

What is the role of the mica glass tape?

It forms the fire barrier around the conductor and supports the cable design for circuit integrity during fire testing.

What does LSZH mean?

Low Smoke Zero Halogen. The sheath is a thermoplastic halogen-free ST8 compound, with smoke and gas test references listed in the fire-performance table.

Which construction sizes are listed?

The construction schedule covers 1.5-1000 mm². Select the exact row for conductor size, diameter and weight.

What mechanical protection does this version use?

Unarmoured construction with a thermoplastic halogen-free ST8 outer sheath. The installation provides additional mechanical protection where required.

What are the conductor temperature limits?

The stated maximum operating temperature is 90°C and the maximum short-circuit temperature is 250°C for 5 seconds.