BS 5467 1900/3300V Single and Three Core XLPE PVC Armoured Cable
BS 5467 1900/3300V XLPE insulated, PVC sheathed armoured cable. Compare single-core and three-core copper or aluminium options across four size tables, with dimensions, weights and selection guidance.
BS 5467 Armoured Power Cables, 1900-3300V.pdf Contact us

APPLICATION

BURY CABLE BS 5467 1900/3300V armoured power cables support fixed power distribution in industrial plants, infrastructure developments, utility installations and building projects. The range combines XLPE insulation, polymeric bedding, wire armour and a PVC outer sheath for routes requiring mechanical protection.

Typical installation routes include outdoor cable runs, ducts and direct burial where the selected cable design meets the project specification and site conditions. Specify the circuit voltage, conductor material, core arrangement and installation method before selecting accessories or confirming a cable size.

This page provides separate parameter tables for single-core copper, single-core aluminium, three-core copper and three-core aluminium cables. Single-core tables specify aluminium wire armour (AWA); three-core tables specify steel wire armour. Use the relevant table for the chosen construction, and confirm electrical ratings and installation requirements for the actual circuit.

CONSTRUCTION

ConductorSolid Aluminum or Annealed Copper conductor, circular or shaped, Class 2 to BS EN60228.
InsulationXLPE (Cross-Linked Polyethylene) Type GP 8 conforming to BS 7655-1.3 or type GP 6 conforming to BS 7655-1.2.
Colour Code1 Core : Brown
3 Cores : Brown, Black, Grey
BeddingThe bedding shall consist of an extruded layer of polymeric material consistent with the operating temperature of the cable.
ArmourSingle Core : AWA (Aluminum Wire Armour)
Multi Core : GSWA (Galvanized Steel Wire Armour)
Outer SheathExtruded PVC, type 9 specified in BS7655-4.2.

TECHNICAL INFORMATION

Voltage rating1900/3300V
Temperature rating0°C to +90°C
Bending radius1.5mm² to 16mm² : 6 x overall diameter
25mm² and above : 8 x overall diameter
Flame retardantBS EN 60332-1-2

CABLE PARAMETER

Single-core 1900/3300 V cables with circular stranded copper conductor

Nominal Cross-sectional AreaStrand TypeNominal Insulation thicknessNominal Bedding thicknessNominal Alum Wire Armor dia.Nominal Sheath thicknessApprox. Overall DiameterAprrox Weight
mm²No./mmmmmmmmmmmmkg/km
1x5019/1.7820.81.251.620.6790
1x7019/2.1420.81.251.622.41040
1x9519/2.5220.81.251.624.31330
1x12037/2.03211.61.727.21680
1x15037/2.25211.61.728.81970
1x18537/2.52211.61.830.82370
1x24061/2.25211.61.833.52960
1x30061/2.52211.61.936.13610
1x40061/2.8521.22240.54600
1x50061/3.202.21.222.144.25680
1x630127/2.522.41.222.248.87160
1x800127/2.852.61.42.52.455.49150
1x1000127/3.202.81.42.52.560.611270

Single-core 1900/3300 V cables with solid aluminum conductor

Nominal Cross-sectional AreaNominal Insulation thicknessNominal bedding thicknessNominal Alum Wire Armor dia.Nominal Sheath thicknessApprox. Overall DiameterAprrox Weight
mm²mmmmmmmmmmkg/km
1x5020.81.251.619.4600
1x7020.81.251.620.9710
1x9520.81.251.622.5810
1x120211.61.725.21065
1x150211.61.726.51210
1x185211.61.828.31390
1x240211.61.830.51630
1x300211.61.932.81900

Three-core 1900/3300 V cables with stranded copper conductors

Nominal Cross-sectional AreaStrand TypeNominal Insulation thicknessNominal Bedding thicknessNominal Steel Wire Armor dia.Nominal Sheath thicknessApprox. Overall DiameterAprrox Weight
mm²No./mmmmmmmmmmmmkg/km
3x167/1.70211.61.829.31600
3x257/2.14211.61.832.22060
3x357/2.52211.61.934.82400
3x35*7/2.52211.61.931.12400
3x50*19/1.7821.22234.73200
3x70*19/2.1421.222.1383800
3x95*19/2.5221.222.241.44730
3x120*37/2.0321.42.52.345.76070
3x150*37/2.2521.42.52.448.57010
3x185*37/2.5221.42.52.551.98270
3x240*61/2.2521.62.52.656.910310
3x300*61/2.5221.62.52.761.212300
3x400*61/2.8521.62.52.966.614500

* Shaped stranded conductor (class 2)

Three-core 1900/3300 V cables with solid aluminum conductors

Nominal Cross-sectional AreaNominal Insulation thicknessNominal Bedding thicknessNominal Steel Wire Armor dia.Nominal Sheath thicknessApprox. Overall DiameterAprrox Weight
mm²mmmmmmmmmmkg/km
3x16211.61.827.91540
3x25211.61.830.41780
3x35211.61.932.72040
3x35*211.61.929.72040
3x50*21.222332760
3x70*21.222.1363210
3x95*21.222.239.13625
3x120*21.42.52.343.14820
3x150*21.42.52.445.65410
3x185*21.42.52.548.76070
3x240*21.62.52.653.27150
3x300*21.62.52.757.28120

* Solid shaped conductor (class 1)

KEY FEATURES

  • 1900/3300V rating, equivalent to 1.9/3.3kV, for the range presented on this page.

  • Single-core circular stranded copper sizes from 50 to 1000 mm² and single-core aluminium sizes from 50 to 300 mm².

  • Three-core stranded copper sizes from 16 to 400 mm² and three-core aluminium sizes from 16 to 300 mm², including the starred conductor variants shown in the tables.

  • AWA construction for the listed single-core cables and steel wire armour for the listed three-core cables.

  • PVC outer sheath, with separate tables for conductor details, insulation and sheath thicknesses, approximate diameters and weights.

  • 46 specification entries across four parameter tables. Values belong to the stated material, core arrangement and complete row designation.

SELECTION NOTES

Start with the correct table. Single-core copper has 13 entries; single-core aluminium has 8; three-core copper has 13; and three-core aluminium has 12. Do not transfer an overall diameter, weight or armour size from a different construction.

Keep asterisks in the specification. In the three-core copper table, the original note identifies starred entries as shaped stranded conductors, Class 2. In the three-core aluminium table, starred entries are solid-shaped conductors, Class 1. The paired 3 x 35 and 3 x 35* rows are distinct variants.

Check the complete circuit design, including load current, route length, voltage drop, fault conditions and installation environment. Overall diameters and weights are approximate. Confirm the final cable drawing, bending requirements, glands, terminations and drum lengths before ordering.

Confirm the conductor form and class, insulation compound and bedding material for the offered design. The family construction table lists material alternatives; the specific parameter table and its notes should be read together with the approved supply specification.

Treat the gallery as construction references. The third cross-section labels a lead alloy protection layer, which is not specified in this page’s standard construction table. Do not assume lead protection is included. Request a separate lead-covered design if that barrier is required.

For quotation, provide voltage, conductor material, number of cores, cross-sectional area and starred variant where applicable, quantity, installation conditions, required standard, sheath colour, packing and delivery destination. State any smoke, halogen, fire-survival or environmental performance requirements separately.

RELATED CABLE TYPES

FAQ

Which conductor sizes and core arrangements are listed?

The four parameter tables cover single-core copper 50–1000 mm², single-core aluminium 50–300 mm², three-core copper 16–400 mm² and three-core aluminium 16–300 mm². There are 46 entries in total, including starred variants. Use the complete row designation when requesting a quotation.

Which armour applies to single-core and three-core cables?

The single-core parameter tables specify aluminium wire armour. The three-core parameter tables specify steel wire armour, and the construction table describes the multicore armour as galvanized steel wire armour. Confirm the required bonding and earthing arrangement with the project design.

What do the asterisks and paired 35 mm² entries mean?

The copper table’s starred entries are shaped stranded conductors, Class 2; the aluminium table’s starred entries are solid-shaped conductors, Class 1. The copper 3 x 35 and 3 x 35* rows list approximate diameters of 34.8 and 31.1 mm. The aluminium equivalents list 32.7 and 29.7 mm. Keep the selected variant explicit.

What temperature and bending information is provided?

The original technical table lists a temperature rating of 0°C to +90°C. It gives a bending radius of 6 times overall diameter for 1.5–16 mm² and 8 times overall diameter for 25 mm² and above. Confirm the limits applicable to the supplied cable, installation temperature and pulling conditions before installation.

Does the illustrated lead alloy layer come with every cable?

No lead layer is specified in this page’s standard construction table. The third gallery image is a reference for a lead-protected variant. If lead protection is required, request a separate construction and confirm its voltage rating, dimensions and supporting technical data.

Is this PVC cable an LSZH or fire-resistant cable?

The listed outer sheath is PVC. LSZH requirements should be assessed using a suitable LSZH construction, such as the linked BS 6724 range. The table lists BS EN 60332-1-2 flame-retardant performance; this page does not establish a fire-survival duration or a CWZ/PH classification. Confirm any required test evidence for the offered cable.

What information is needed for a quotation?

Send the 1900/3300V rating, copper or aluminium conductor, single-core or three-core arrangement, size and starred variant, required length, installation environment, project standard, packing and delivery destination. Include any specific sheath, smoke, fire or chemical-protection requirements so the offered construction can be checked.